fIgURE 3. TyPICAL 2-WIRE INITIATINg CIRCUIT CONfIgURATION, NfPA STyLE B:

(+)

(–)

(+)

(–)

(+)

(–)

MONITOR 

MODULE

ANY NUMBER OF UL LISTED 

CONTACT CLOSURE DEVICES 

MAY BE USED. DO NOT MIX FIRE 

ALARM INITIATING, 

SUPERVISORY, OR SECURITY 

DEVICES ON THE SAME MODULE.

TO NEXT 

DEVICE

FROM PANEL OR 

PREVIOUS DEVICE

47K EOL 

RESISTOR 

ELR-47K

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

INITIATING DEVICE CIRCUIT (IDC) - NFPA STYLE B 

POWER LIMITED: 400µA MAX. @ 11 VDC MAX

INSTALL CONTACT CLOSURE DEVICES PER 

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

C1051-00

fIgURE 4. TyPICAL 4-WIRE fAULT TOLERANT INITIATINg CIRCUIT CONfIgURATION, NfPA STyLE D:

(+)

(-)

(+)

(–)

(+)

(–)

MONITOR 

MODULE

TO NEXT 

DEVICE

FROM PANEL OR 

PREVIOUS DEVICE

CONNECT MODULES TO LISTED 

COMPATIBLE CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED

ANY NUMBER OF UL LISTED 

CONTACT CLOSURE DEVICES 

MAY BE USED. DO NOT MIX FIRE 

ALARM INITIATING, 

SUPERVISORY, OR SECURITY 

DEVICES ON THE SAME MODULE.

INSTALL CONTACT CLOSURE DEVICES PER 

MANUFACTURER’S INSTALLATION INSTRUCTIONS.

EOL RESISTOR 

IS INTERNAL AT 

TERMINALS

8 AND 9

C0919-03