MIX-M500MAP Monitor Module

INSTALLATION AND MAINTENANCE INSTRUCTIONS

BEfORE INSTALLINg

This information is included as a quick reference installation guide. Refer to 

the control panel installation manual for detailed system information. If the 

modules will be installed in an existing operational system, inform the opera-

tor and local authority that the system will be temporarily out of service. Dis-

connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.

gENERAL DESCRIPTION

The MIX-M500MAP Monitor Module is intended for use in intelligent, two-

wire systems, where the individual address of each module is selected using 

the built-in rotary decade switches. It provides either a 2-wire or 4-wire fault 

tolerant initiating circuit for normally open contact fire alarm, supervisory, or 

security devices. The module has a panel controlled LED indicator.

COMPATIBILITy REqUIREMENTS

To ensure proper operation, these modules shall be connected to listed com-

patible system control panels only.

fIgURE 1. CONTROLS AND INDICATORS:

C0917-01

SPECIfICATIONS

Normal Operating Voltage: 

15 to 32 VDC

Maximum Alarm Current (LED on): 

5.0mA (LED on)

Average Operating Current: 

400 μA, 1 communication every 5 seconds, 47k EOL

EOL Resistance: 

47K Ohms

Maximum IDC wiring resistance: 

40 Ohms

Maximum IDC Voltage: 

11 Volts

Maximum IDC Current: 

400µA

Temperature Range: 

32˚F to 120˚F (0˚C to 49˚C)

Humidity: 

10% to 93% Non-condensing

Dimensions: 4

1

/

2

˝ H x 4˝ W x 1

1

/

4

˝ D (Mounts to a 4˝ square by 2

1

/

8

˝ deep box.)

Accessories: 

SMB500 Electrical Box

MOUNTINg

The MIX-M500MAP mounts directly to 4-inch square electrical boxes (see 

Figure  2).  The  box  must  have  a  minimum  depth  of  2

1

/

8

 inches. Surface 

mounted electrical boxes (SMB500) are available from System Sensor.

fIgURE 2. MODULE MOUNTINg:

ISOLATED

QUADRANT

C1044-00

WIRINg

NOTE: All wiring must conform to applicable local codes, ordinances, and 

regulations. This module is intended for power limited wiring only.
1.   Install module wiring in accordance with the job drawings and appropri-

ate wiring diagrams.

2.  Set the address on the module per job drawings.
3.   Secure module to electrical box (supplied by installer), as shown in Fig-

ure 2.