2
3
Relay Functionality
The relay is operated by setting output bit 0. If the supply voltage is removed, the relay
will not change state. When the Relay Output Module is powered up, the relay will be
in the same state as it was prior to the module being switched off but the module will
respond to output bit 0 four seconds after power has been applied. If the module has
not been interrogated, a relay reset will automatically be applied.
Address Setting
Segments 1-7 of the DIL Swtich are used to select the address of the module. Each of
the seven segments must be set to ‘0’ (ON) or ‘1’ (OFF) using a small screwdriver or
similar tool. A complete list of address settings is shown below.
DIL switch
DIL switch
DIL switch
DIL switch
DIL switch
addr
setting addr
setting addr
setting addr
setting addr
setting
1234567
1234567
1234567
1234567
1234567
1
1000000 11
1101000 21
1010100 31
1111100 41
1001010
2
0100000 12
0011000 22
0110100 32
0000010 42
0101010
3
1100000 13
1011000 23
1110100 33
1000010 43
1101010
4
0010000 14
0111000 24
0001100 34
0100010 44
0011010
5
1010000 15
1111000 25
1001100 35
1100010 45
1011010
6
0110000 16
0000100 26
0101100 36
0010010 46
0111010
7
1110000 17
1000100 27
1101100 37
1010010 47
1111010
8
0001000 18
0100100 28
0011100 38
0110010 48
0000110
9
1001000 19
1100100 29
1011100 39
1110010 49
1000110
10
0101000 20
0010100 30
0111100 40
0001010 50
0100110
51
1100110 61
1011110 71
1110001 81
1000101 91
1101101
52
0010110 62
0111110 72
0001001 82
0100101 92
0011101
53
1010110 63
1111110 73
1001001 83
1100101 93
1011101
54
0110110 64
0000001 74
0101001 84
0010101 94
0111101
55
1110110 65
1000001 75
1101001 85
1010101 95
1111101
56
0001110 66
0100001 76
0011001 86
0110101 96
0000011
57
1001110 67
1100001 77
1011001 87
1110101 97
1000011
58
0101110 68
0010001 78
0111001 88
0001101 98
0100011
59
1101110 69
1010001 79
1111001 89
1001101 99
1100011
60 0011110
70 0110001
80 0000101
90 0101101
100 0010011
101 1010011
111 1111011
121 1001111
102 0110011
112 0000111
122 0101111
103 1110011
113 1000111
123 1101111
104 0001011
114 0100111
124 0011111
105 1001011
115 1100111
125 1011111
106 0101011
116 0010111
126 0111111
107 1101011
117 1010111
108 0011011
118 0110111
109 1011011
119 1110111
110 0111011
120 0001111
ON
1
5
4
3
2
64
32
16
8
4
2
1
7
6
0
1
ADDRESS
Fig 1. Mounting the Alpha Relay Output Module
Fig 2. Wiring Diagram for Alpha Relay Output Module
Fig 3. DIL Switch
{
{
L1 (–)
L2 (+)
RELAY OUTPUT MODULE
LOOP IN
LINES
LOOP OUT
LINES
N/C
COM
N/O
ON
1
5
4
3
2
64
32
16
8
4
2
1
7
6
N/O
COM
N/C
RELAY CONTACTS
CONNECT AS REQUIRED
RELAY CONTACTS