Alpha Relay Output Module 

Installation Instructions

General

The Alpha Relay Output Module, part no MIX-100R, is a loop-powered device which 

incorporates a dual form C, volt-free relay output. It is mounted on a plastic fascia 

plate for use with a 4" electrical box.

A red LED 

fl

 ashes in synchronization with the current pulse reply from the device. If 

output bit 2 is set, the LED is illuminated continuously.

Note: the Alpha Relay Output Module is not designed for outdoor use unless it is 

mounted in a suitable weatherproof enclosure.

Control Panel Compatibility

Compatibility Identi

fi

 er number: MIX-100R. The module has been approved by Under-

writers Laboratories Inc. For details of compatible control panels contact Apollo Fire 

Detectors Limited.

Installation

These products must be installed in accordance with the applicable NFPA standards, 

local codes and jurisdictional authorities. Failure to follow these instructions may 

result in failure of devices to report an alarm condition. Apollo Fire Detectors Limited 

is not responsible for devices which are improperly installed, maintained and tested.

Before installing these products, check the continuity, polarity and insulation resist-

ance of all wiring. Check that siting is in accordance with the 

fi

 re system drawings 

and conforms to all applicable local codes such as NFPA 72.

1.  Mount the electrical box as required and install all cables for termination. Ensure 

that cable shield/earth continuity is maintained.

2.  Terminate all cables in compliance with local codes and regulations.

3.  Set the address of the module as shown on page 3.

4.  Drill holes in the fascia plate corresponding to the holes on the mounting box 

selected  

(Fig 1).

5.  Gently push the completed assembly towards the mounting box and align the 

fi

 xing holes. Secure the unit with the screws provided. Do not overtighten the 

screws.

6.  Commission the module.

39214-395/Issue 1 Draft B

Note

1. All circuits are power limited except for relay contacts. If the relay contacts are 

connected to a non power limited source, remove the lower portion of the power 

limited label along the kiss cut. Use only limited energy cable types FPL, FPLR or FPLP 

on power limited circuits.

Technical Data

Part No

MIX-100R

Compatability Identifi er

MIX-100R

Type

Relay Output Monitor

Style

Fascia Plate with wiring terminals

Dimensions

4½" x 4½" x 1"

Temperature Range

32°F to 120°F (0°C to 49°C)

Humidity

10 to 93% RH non-condensing

Signal Line Circuit (SLC)

Supervised

     Working Voltage

17–28V DC

Modulation Voltage (peak to peak)

9-5V

Supervisory Current

0.85mA

Surge Current

2.5mA

Maximum Alarm Current LED on

3.5mA

Max Line Impedance

50

Ω

 max

Functional States

     Analog Levels: Normal

16

Relay Output

Non Supervised, dry contact;

24VDC, 2A; 30VAC, 0.5A

Functional Test Data

Output 

Bit

Function

Input 

Bit

Function

2

Alarm  LED

1 = On

0 = Off

2

Alarm LED Con

fi

 rmation

1 = On

0 = Off

1

Not Used

1

Not Used

0

Relay  Control

1 = On

0 = Off

0

Relay  Con

fi

 rmation

1 = On

0 = Off

LT-1031 Rev.1

February 2010