Press on any key to start the process (see figure 1 for key locations). 
The programmer will start up and will display the last address that 
was read or written. To read the current device address, press on the 
Read key (showing a magnifier and red X). If the address has to be 
modified, use the up and down keys at the left. To program the 
displayed address in the device, press on the Write key (showing a 
pen & paper symbol and a green check mark).

Once the address is programmed in the device, remove it from the 
programmer by twisting it counter clockwise.  Most projects require 
that a device address must be visible for inspection: MIX-4000 bases 
have a breakable tab that can be inserted on the outside of the base 
to show the address. See MIX-40XX installation sheet for details.

Address programming (Permanently installed devices):

Warning: Do not disconnect a device during address storing 
operation. This may damage the device.

Plug the programming cable in the MIX-4090 using the connector on 
top, shown in figure 4. Locate the programming connector on the 
device, see figure 5. If the device is already installed, it may be 
necessary to remove the wall plate covering the device to access the 
connector. 

FIGURE 4   PROGRAMMER CABLE ATTACHMENT

Unless the device has to be replaced, there is no need to disconnect 
wires from it. However the whole SLC line should be disconnected 
from the loop driver when devices are programmed while in place. If 
the SLC line is powered, the programmer may be unable to read or 
write the device data.

Connect the cable to the device (see figure 5): Please note that the 
programming plug is polarized to ensure that it is inserted in the cor-
rect position. Then proceed as above to read and set addresses. 
When done, use a pen or labels  to indicate the device address as 
required by the project.

FIGURE 5   CABLE ATTACHMENT TO DEVICE

Reading device parameters: 

Several device parameters can be read though the MIX-4090 
programmer. First the device must be connected to the programmer 
as described for address setting. After the programmer is turned on 
and is showing the address screen, press on the “Read” key for 
about five seconds. The message “Family 

 Analog” should appear. 

If “Family  

 Conv” is shown, use the up-down keys to get to “Family 

 Analog” . When done, press on the “Write” key to enter the sub-

menus.

The following parameters can then be accessed using the up and 
down keys: 

·

Device type: “DevType” followed by device type. See table 
1 for a full list of devices.

·

Series: Mircom should be displayed.

·

Customer: This parameter is not used.

·

Battery: remaining battery capacity

·

Test Date: “TstDate” followed by date of device testing in 
production

·

Production Date: “PrdDate” followed by date of device 
fabrication 