background image

 

LT

6138

 

rev

 

1.1

  

7/16/19

         

25 Interchange way, Vaughan Ontario. L4K 5W3

Phone: 905.660.4655; Fax: 905.660.4113

INSTALLATION AND MAINTENANCE INSTRUCTIONS

Web:  www.mircom.com

MIX-4030 HEAT DETECTOR
MIX-4030-ISO HEAT DETECTOR

                                                                  

ABOUT THIS MANUAL

This manual is included as a quick reference for installation.  For fur-
ther information on the use of this device with a FACP, please refer to 
the panel’s manual.  For more information regarding maintenance, 
testing, spacing, and locating detectors, please refer to the LT-9420 
MIX-4000 series detector technical bulletin.
Note:  This manual should be left with the owner/operator of this 
equipment

DETECTOR DESCRIPTION

The MIX-4030 heat detector continuously  measure ambient 
temperature and reports it to the Fire-Alarm panel using a fully digital 
communication protocol. It can be set to report an alarm when 
sampled temperature exceeds 135F (57C) or 175F (79C).   
Excessive temperature rises can also be reported if the detector is 
configured for rate-of-rise operation.  The MIX-4030 must be used 
with a Mircom series 4000 compatible control panel.  Operation 
mode is selected at the Fire alarm panel through the Mircom 
configuration tool.  It also has a remote output that can be controlled 
by the panel.  Please see specifications for compatible devices that 
can use the remote output feature.
Note: MIX-4030-ISO is equipped with a bi-directional short-circuit 
isolator to help protect against wiring faults that may otherwise result 
in a loop failure.
Before installing this device please thoroughly read this manual and 
refer to the applicable codes for guidance on location, spacing and 
acceptable use.  Also seek guidance from the compatible control 
panel instructions for the device operation modes and the 
configuration requirements.
Note: If the detector is used with the remote indicator, then the 
voltage value of the detector must be at least 18V as the indicators 
do not operate below 18V

FIGURE 1   DETECTOR FRONT:

SPECIFICATIONS

Normal Operating Voltage:

15 to 30VDC

Maximum Alarm Current (LED on):

3.2mA (LED on)

Standby Current:

160uA (LED flashing)

Maximum Input Wiring Resistance:

40 Ohms

Temperature Range (no alarm):

32F to 100F (0C to 37.8C)

Humidity:

10% to 93% Non-condensing

Dimensions:

4 1/4” Diameter, 1 3/4” Height

Mounting:

4” square by 2 1/8” deep box

Accessories:

MIX-4090 Programmer
MIX-4001/4002 Detector Base
RA100Z Remote LED

Wiring range on all terminals:

22 to 12 AWG

INSTALLATION

This detector must be installed on a ceiling or wall using a compatible 
base.  SLC line and remote output connections for the most common 
base MIX-4001 are show in figure 2.  A twisted pair cable should be 
used for the SLC line.  If a shielded cabled is used, connect the 
shields to the proper terminal on the base.  Do not connect shields to 
earth ground.  If a ground continuity wire is required by the local 
code, it should be a separate conductor.  Please note that shielded 
cables may reduce the SLC loop length that can be achieved due to 
their high capacitance.

The detector address should be programmed using the MIX-4090 

hand-held device before inserting the detector on the base.  
Addresses 1 to 240 can be used for any device on a SLC loop.  Each 
device on a loop must have a unique address.
A breakaway tab inside the base can be inserted in the outer rim of 
the base to visibly identify each detector with their address. See 
figures 2 and 4.  The detector can then be placed on the base using 
the following steps:
1. Position the detector centrally on its adapter base ensuring it is 
level.
2. Rotate clockwise applying gentle pressure. The detector will drop 
into its keyed location.
3. Continue to rotate clockwise a few degrees until the detector has 
fully engaged in the adaptor base.
4. When the detector is firmly engaged, check the alignment of the 
raised reference marks on the detector and on the base (figure 4).

IMPORTANT NOTES ON DETECTOR INSTALLATION

Disconnect loop power before installing the detector.
This detector comes with a dust cover to protect the device during 
shipping and when first installed. It is not intended to provide 
complete protection against contamination, therefore, detectors 
should be removed from their base before construction, major re-
decoration or other dust producing work is started. Dust covers must 
be removed before the system becomes operational.
Heat detectors should installed away from normal heat sources. Do 
not use in locations where ambient temperature is within 20F (10C) 
of the alarm setting. Long term ambient temperature should not 
exceed 120F (49C).
When configured for rate of rise operation, do not use heat detectors 
in locations such as an heated building entrance where large 
temperatures swings can be expected.
Smoke detectors are not to be used with detector guards unless the 
combination has been evaluated and found suitable for that purpose.
When duplicate terminals are not provided to facilitate monitoring of 
the installation wiring connections, and there is no provision to 
prevent looping an unbroken wire around or under a terminal, the 
word "CAUTION" and the following or equivalent text in letters not 
less than 2.38 mm (3/32 inch) high shall be included on the 
installation drawing: "FOR SYSTEM MONITORING - FOR 
TERMINALS "Loop out (+)"  AND "Remote Device (+)", DO NOT 
USE LOOPED WIRE UNDER TERMINALS. BREAK WIRE RUN TO 
PROVIDE MONITORING OF CONNECTIONS.

Reviews: