Mircom
10
Electrical Specifications
RAXN-LCD Remote LCD Annunciator
• 24V DC nominal.
• Provides exact functions as the MNS main display.
• Standby: 139 mA Max., All LEDs ON: 164 mA Max.
RAX-1048TZDS
• 24V DC nominal.
• Provides audio activity indication at each FX-LOC.
• Standby: 22 mA Max., one LED ON 26mA, All LEDs ON: 262 mA Max.
• Only one LED can be ON at any time.
QMP-5101N Master Microphone Paging Module
• Interconnects between other QMP-5101N module at the MNS and within the associated FX-LOC(R)s
• Standby: 175 mA Max., Alarm: 175 mA Max.
Current Drain for Battery Calculations (Example)
The following are the currents for the RAXN-LCD to which is added to the RAX-1048TZDS plus QMP-5101N for a
total current per FX-LOC(R):
Normal Standby Current
= 139 mA + 22 mA + 175mA = 336 mA
Maximum
Alarm
Current
= 164 mA + 26 mA + 175mA = 365mA
The
Normal Standby Current
is used for battery size calculations to add to the main Fire Alarm Panel (see the
FleX-Net
TM
Manual for additional battery calculations) and includes the current drain for the Trouble Buzzer, Trouble
LED, and one alarm LED.