background image

Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: 905-660-4655 Fax: 905-660-4113

 Mircom 200

6

Printed in Canada
Subject to change without prior notice

www.mircom.com

FA-101T

Fire Alarm Control Panel

LT-513 Rev. 

6

Janua

r

y

 200

6

Installation and Operation Manual

Advanced Life Safety Solutions

Advanced Life Safety Solutions

A.C. ON

SIGNAL

SILENCED

1

U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113

Summary of Contents for FA-101T

Page 1: ...FA 101T Fire Alarm Control Panel LT 513 Rev 6 January 2006 Installation and Operation Manual Advanced Life Safety Solutions A C ON SIGNAL SILENCED 1...

Page 2: ......

Page 3: ...LED 3 Ground Fault LED 3 Signal Trouble LED 3 Sequence of Operation 4 Normal 4 Alarm 4 Signal Silence 4 Reset Lamp Test 4 System Checkout 4 Power up and Troubleshooting 4 Wiring Tables and Information...

Page 4: ...Mounting details 5 Figure 2 Circuit Board Layout 6 Figure 3 Detection and Signal Wiring 7 Figure 4 Wiring Table for Detection Zone 8 Figure 5 Wiring Table for Bells and Horns 8 Figure 6 Alarm and Tro...

Page 5: ...face Mounting 1 Mark the location of the four mounting holes 2 Install the top two screws into the wall and place the panel over the screws 3 Install the bottom screws and tighten down all four screws...

Page 6: ...ignal zone available for bells and horns providing 1 7A of signal power Refer to Figure 3 on page 7 for wiring instruction and to Figure 5 page 8 on for wire size Alarm and Trouble Relays Alarm and tr...

Page 7: ...d for any trouble in the panel unless DSW1 8 is ON then the Common Trouble LED will illuminate steadily and the buzzer will sound Buzzer Buzzer Silence Switch The buzzer will sound intermittently for...

Page 8: ...anel to preform a lamp test as well as reset the panel System Checkout Before turning the power on 1 Check all external wiring for opens shorts or grounds 2 Check that transformer cables are securely...

Page 9: ...5 Figure 1 Backbox and Flush Trim Mounting details 13 3 4 12 3 4 1 11 16 Optional flush mounting trim model FA 102TR Four 7 32 dia mounting holes 2 7 8 7 1 8 1 1 4 10 3 8...

Page 10: ...TRB A C ON 24V 1 1 JW3 JW4 TRBL ALARM ZONE 1 A C ON TRBL SIG SIL BATT GND TRANSFORMER P1 P2 P3 BATTERY P4 SIG 1 F1 2A BATTERY A C 2A F2 1 COM JW2 JW1 AUX TRBL ON DSW1 DIP SWITCHES 1 8 MD 738 DETECTIO...

Page 11: ...iring Legend Pull Station Smoke Detector Heat Detector Bell F F S R Alarm threshold current is 21 mA Maximum loop resistance is 100 ohms ELR 3 9K 1 2W F S R TB2 Detection zone F F ELR 3 9K 1 2W Signal...

Page 12: ...istance should not exceed 100 ohms Total Signal Load Maximum Wiring Run to Last Device ELR Max Loop Resistance 18AWG 16AWG 14AWG 12AWG 0hms Amperes ft m ft m ft m ft m Ohms 0 06 2350 716 3750 1143 600...

Page 13: ...s Auxiliary common alarm relay contacts 28VDC 3A resistive Common trouble relay contacts 28VDC 3A resistive Cut JW3 for N O Cut JW4 for N C N O C N C TS2 TRL TRB A C ON 24V 24VDC 250 mA max 24VDC 50 m...

Page 14: ...1 70 201000 003 1400 A PSD 7131 70 201000 005 2400 A Mirtone PSD 7130 70 201000 001 1451 A B401B 73471 PSD 7130 70 201000 002 1451 A B406B 73494 PSD 7130 70 201000 003 2451 A B401B 73575 PSD 7130 70 2...

Page 15: ...odel Base Compatibility Identifier Head Base Rated Standby Current System Sensor Sentrol ESL 1100 A N A 0 12 mA 429C S10A N A 0 10 mA 1151 B110LP A A 0 12 mA 429CT S10A N A 0 10 mA 1151 B116LP A A 0 1...

Page 16: ...mA 2400TH A N A 0 12 mA 2400AT A N A 0 12 mA Detection Systems Inc 2400AIT A N A 0 12 mA DS250 B N A 0 10 mA 2451 B401B A A 0 12 mA DS250TH B N A 0 10 mA 2451 B406B A A 0 12 mA DS282 B N A 0 10 mA 24...

Page 17: ...SS 241575W FR RSS 2415W FR RSS 241575W FR RSS 2430W FR RSS 2475W FR RSS 24110W FR RSS 2415C FW RSS 2430C FW RSS 2475C FW RSS 24100C FW MT 12 24 ULC MT 24 LS VFR ULC MT 24 WS VFR ULC AMT 12 24 R ULC AM...

Page 18: ...ORTANT NOTICE The main AC branch circuit connection for the fire alarm control unit must provide a dedicated continuous power without provision of any disconnect devices Use 12 AWG wire with 600 volt...

Page 19: ...hall not be responsible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted by...

Page 20: ...5W3 Tel 905 660 4655 Fax 905 660 4113 Mircom 2006 Printed in Canada Subject to change without prior notice www mircom com Advanced Life Safety Solutions U S A 60 Industrial Parkway Cheektowaga NY 142...

Reviews: