7.0 Field Wiring
18
7.5 Wiring Tables & Information
Table 1: Wiring Table for Input Circuits
Table 2: Wiring Table for Indicating Circuits
Auxiliary Power Wiring
Table 2: Wiring Table for Indicating Circuits
above.
Wire Gauge
Maximum Wiring Run to Last Device (ELR)
(AWG)
ft
m
22
2990
910
20
4760
1450
18
7560
2300
16
12000
3600
14
19000
5800
12
30400
9200
Note:
Maximum Loop Resistance Should Not Exceed 100 Ohms
TOTAL
SIGNAL
LOAD
MAXIMUM WIRING RUN TO LAST DEVICE (ELR)
MAX. LOOP
RESISTANCE
18AWG
16AWG
14AWG
12AWG
Amperes
ft
m
ft
m
ft
m
ft
m
Ohms
0.06
2350
716
3750
1143
6000
1829
8500
2591
30
0.12
1180
360
1850
567
3000
915
4250
1296
15
0.30
470
143
750
229
1200
366
1900
579
6
0.60
235
71
375
114
600
183
850
259
3
0.90
156
47
250
76
400
122
570
174
2
1.20
118
36
185
56
300
91
425
129
1.5
1.50
94
29
150
46
240
73
343
105
1.2
1.70
78
24
125
38
200
61
285
87
1.0
Note:
Main Board Indicating Circuits are rated for 1.7 Amperes each.SGM-1004A Indicating Circuits are
rated for 1.7 Amperes each.
Note:
Maximum Voltage Drop Should Not Exceed 1.8 Volts