Safety precautions for installing and relocating the unit

To ensure safety, please be mindful of the following precautions. 

• When installing or relocating the unit, be sure to keep the refrigerant 

circuit free from air or substances other than the specified refrigerant. 

 

Any presence of air or other foreign substance in the refrigerant circuit will 

cause system pressure rise or compressor rupture, resulting in injury.  

• When installing or moving this unit, do not charge the refrigerant which 

is not comply with that on the nameplate or unqualified refrigerant. 

 

Otherwise, it may cause abnormal operation, wrong action, mechanical mal-

function or even series safety accident.  

• When refrigerant needs to be recovered during relocating or repairing 

the unit, be sure that the unit is running in cooling mode.Then, fully 

close the valve at high pressure side (liquid valve).About 30-40 seconds 

later, fully close the valve at low pressure side (gas valve), immediately 

stop the unit and disconnect power. Please note that the time for refriger-

ant recovery should  not exceed 1 minute.  

If refrigerant recovery takes too much time, air may be sucked in and cause 

pressure rise or compressor rupture, resulting in injury.  

• During refrigerant recovery, make sure that liquid valve and gas valve 

are fully closed and power is disconnected before detaching the connec-

tion pipe.

  

If compressor starts running when stop valve is open and connection pipe is 

not yet connected, air will be sucked in and cause pressure rise or compressor 

rupture, resulting in injury. 

• When installing the unit, make sure that connection pipe is securely 

connected before the compressor starts running.

 

If compressor starts running when stop valve is open and connection pipe is 

not yet connected, air will be sucked in and cause pressure rise or compressor 

rupture, resulting in injury. 

• Prohibit installing the unit at the place where there may be leaked 

corrosive gas or flammable gas. 

If there leaked gas around the unit, it may cause explosion and other 

accidents. 

• Do not use extension cords for electrical connections. If the electric 

wire is not long enough, please contact a local service center authorized  

and ask for a proper electric wire. 

Poor connections may lead to electric shock or fire.

 

• Use the specified types of wires for electrical connections between the 

indoor and outdoor units. Firmly clamp the wires so that their terminals 

receive no external stresses.

Electric wires with insufficient capacity, wrong wire connections and insecure 

wire terminals may cause electric shock or fire.

WARNING

Summary of Contents for IAXH090A

Page 1: ...oper operation please read and keep this manual carefully If you have lost the Owner s Manual please visit www mirageappliances us IAXH090A OAXH090A IAXH120A OAXH120A IAXH121A OAXH121A IAXH181A OAXH18...

Page 2: ...t if not avoided could result in death or serious injury Indicates a hazardous situation that if not avoided may result in minor or moderate injury Indicates important but not hazard related informati...

Page 3: ...acuum pumping Leakage detection Check after installation Test and operation Test operation Attachment Configuration of connection pipe Pipe expanding method 1 6 8 8 9 13 15 15 16 16 19 23 24 25 25 26...

Page 4: ...e electric shock If the supply cord is damaged it must be replaced by the manufacturer its service agent or similarly qualified persons in order to avoid a hazard Do not wash the air conditioner with...

Page 5: ...r cord is overheating or damaged There s abnormal sound during operation Circuit break trips off frequently Air conditioner gives off burning smell Indoor unit is leaking If the air conditioner operat...

Page 6: ...rcuit break with suitable capacity please note the following table Air switch should be included magnet buckle and heating buckle function it can protect the circuit short and overload Air Conditioner...

Page 7: ...d personnel only The air conditioner is a first class electric appliance It must be properly grounding with specialized grounding device by a professional Please make sure it is always grounded effect...

Page 8: ...ause personal injury or damage Select a location which is out of reach for children and far away from animals or plants If it is unavoidable please add the fence for safety purpose The indoor unit sho...

Page 9: ...r Unit Outdoor Unit Actual product may be different from above graphics please refer to actual products air inlet Connection wire air outlet air inlet panel aux button horizontal louver air outlet NOT...

Page 10: ...r some model heating indicator temp indicator cooling indicator power indicator receiver window drying indicator display For some model heating indicator temp indicator cooling indicator power indicat...

Page 11: ...tton TEMP button I FEEL button LIGHT button CLOCK button TIMER ON TIMER OFF button SLEEP button Send signal Turbo mode 46 F heating function Set temperature Set time TIMER ON TIMER OFF Child lock Up d...

Page 12: ...corresponding set function icons Press this button can turn on or turn off the air conditioner After turning on the air conditioner operation indicator on indoor unit s display is ON green indicator T...

Page 13: ...r conditioner will select proper fan speed automatically according to ex factory setting Fan speed under dry mode is low speed Press this button can select up down swing angle Fan blow angle can be se...

Page 14: ...o CLOCK TIMER ON TIMER OFF buttons Under COOL HEAT or DRY mode press this button to start up sleep function icon is displayed on remote controller Press this button again to cancel sleep function and...

Page 15: ...indoor unit can receive the signal sent by the remote controller Press this button to turn off display light on indoor unit icon on remote controller disappears Press this button again to turn on dis...

Page 16: ...ff according to setting time ON OFF button has no effect on setting If you don t need this function please use remote controller to cancel it Function introduction for combination buttons Energy savin...

Page 17: ...TURBO button and the remote controller won t send signal Sleep function and 46 F heating function can t operate at the same time If 46 F heating function has been set under cooling mode press sleep b...

Page 18: ...e two 7 AAA 1 5V dry batteries and make sure the position of polar and polar are correct 3 Reinstall the cover of battery box During operation point the remote control signal sender at the receiving w...

Page 19: ...mode Use insulated object to press the auto button Clean and Maintenance Turn off the air conditioner and disconnect the power before cleaning the air conditioner to avoid electric shock Do not wash...

Page 20: ...ry dirty use the water below 110 F to clean it and then put it in a shady and cool place to dry Install filter Install the filter and then close the panel cover tightly The filter should be cleaned ev...

Page 21: ...and Maintenance Checking before use season 1 Disconnect power supply 2 Clean filter and indoor unit s panel 3 Check whether mounting bracket for outdoor unit is damaged or corroded If yes please conta...

Page 22: ...n troller low fuzzy display and no display Check the batteries If the power of batteries is too low please replace them No display when operating remote controller Check whether remote control ler app...

Page 23: ...indoor unit s air outlet Indoor temperature and humidity is high Because indoor air is cooled rapidly After a while indoor temperature and humidity will be decrease and mist will disappear Set tempera...

Page 24: ...t again Outdoor unit has vapor Heating mode is turned on During defrosting under heating mode it may generate vapor which is a normal phe nomenon Water flowing noise Air conditioner is turned on or tu...

Page 25: ...alified professionals for service C5 Please contact qualified professionals for service F1 Please contact qualified professionals for service F2 Please contact qualified professionals for service F0 P...

Page 26: ...At least 20 At least 12 At least 118 At least 80 Space to the obstruction Space to the obstruction Space to the obstruction Space to the ceiling Space to the obstruction Space to the obstruction At le...

Page 27: ...ure resulting in injury During refrigerant recovery make sure that liquid valve and gas valve are fully closed and power is disconnected before detaching the connec tion pipe If compressor starts runn...

Page 28: ...hould be no obstruction near air inlet and air outlet 2 Select a location where the condensation water can be dispersed easily and won t affect other people 3 Select a location which is convenient to...

Page 29: ...y the manufacturer its service agent or similarly qualified persons in order to avoid a hazard 8 The temperature of refrigerant circuit will be high please keep the interconnection cable away from the...

Page 30: ...piping hole 1 Choose the position of piping hole according to the direction of outlet pipe The position of piping hole should be a little lower than the wall mounted frame shown as below 2 Open a pipi...

Page 31: ...ding out the pipe from left or right please cut off the corresponding hole on the bottom case Step five connect the pipe indoor unit 1 Aim the pipe joint at the corre sponding bellmouth 2 Pretightenin...

Page 32: ...in hose 1 Connect the drain hose to the outlet pipe of indoor unit 2 Bind the joint with tape outlet pipe drain hose drain hose tape outlet pipe drain hose insulating pipe Note Add insulating pipe in...

Page 33: ...for reference only please refer to the actual one Note All wires of indoor unit and outdoor unit should be connected by a professional If the length of power connection wire is insufficient please co...

Page 34: ...d and control wire can t be crossed or winding The drain hose should be bound at the bottom Step nine hang the indoor unit 1 Put the bound pipes in the wall pipe and then make them pass through the wa...

Page 35: ...stalled at least 2 above the floor in order to install drain joint For the unit with cooling capacity of 2300W 5000W 6 expansion screws are needed for the unit with cooling capacity of 6000W 8000W 8 e...

Page 36: ...signal control wire only for cooling and heating unit to the wiring terminal according to the color fix them with screws Note the wiring board is for reference only please refer to the actual one Ins...

Page 37: ...d along the wall bent reasonably and hidden possibly Min semidiameter of bending the pipe is 10cm 2 If the outdoor unit is higher than the wall hole you must set a U shaped curve in the pipe before pi...

Page 38: ...OFF to check if pressure keeps stable If not you must look for leakage fix and try again 5 If vacuum level is stable use an Allen wrench to open gas and liquid valves completely to let refrigerant fi...

Page 39: ...the speci cation It may cause malfunction or damaging the parts Is there any obstruction in the air inlet and outlet It may cause insuf cient cooling heat ing capacity The dust and sundries caused dur...

Page 40: ...ft 65 ft 48000Btu h 14064W 98 ft 65 ft 4 The additional refrigerant oil and refrigerant charging required after prolonging connection pipe After the length of connection pipe is prolonged for 32 ft at...

Page 41: ...7C R410A and R134a Diameter of connection pipe Outdoor unit throttle Liquid pipe Gas pipe Cooling only oz ft Cooling and heating oz ft 1 4 3 8 or 1 2 0 161 0 215 1 4 or 3 8 5 8 or 3 4 0 161 0 537 1 2...

Page 42: ...move the union nut on the indoor connection pipe and outdoor valve install the union nut on the pipe E Expand the port Expand the port with expander Note A is different according to the diameter pleas...

Page 43: ...5 Compressor demagnetization protection HE Over phase current protection P5 PFC protection Hc Compressor desynchronizing H7 IPM Temperature Protection P8 IPM Current protection H5 Over power protectio...

Page 44: ...6700 Gateway Park Dr Unit 6 San Diego CA 92154 Ph 619 426 0033 mirageappliances us...

Reviews: