Minuteman MBK 300YYY User Manual Download Page 2

0 - 135 (0 - 270) VAC

105 - 136 (175 - 270) VAC
105 - 136 (210 - 250) VAC

6

REP

LACING THE BATTERY

R

EPLACING 

T

HE 

B

ATTERY

The MBK Series UPS has an easy to replace hot-swappable battery. Please read the

following warning statements before attempting to service the battery.

WARNING!

        THIS UNINTERRUPTIBLE POWER SOURCE CONTAINS POTENTIALLY

HAZARDOUS VOLTAGES. DO NOT ATTEMPT TO DISASSEMBLE THE UNIT

BEYOND BATTERY REPLACEMENT PROCEDURES BELOW. EXCEPT FOR

THE BATTERY, THIS UPS CONTAINS NO USER SERVICABLE PARTS.

REPAIRS CAN BE PERFORMED BY MINUTEMAN SERVICE PERSONNEL

ONLY

     DO NOT OPEN OR MUTILATE BATTERIES. RELEASED ELECTROLYTE

IS HARMFUL TO THE SKIN AND EYES AND MAY BE TOXIC

CAUTION:

CAUTION:

CAUTION:

THE BATTERIES IN THIS UPS ARE RECYCLABLE. DISPOSE OF THE

BATTERIES PROPERLY. THE BATTERIES CONTAIN LEAD AND POSE A

HAZARD TO THE ENVIRONMENT AND HUMAN HEALTH IF NOT DISPOSED

OF PROPERLY. REFER TO LOCAL CODES FOR PROPER DISPOSAL

REQUIREMENTS OR RETURN THE BATTERY TO MINUTEMAN.

ALTHOUGH BATTERY SYSTEM VOLTAGES ARE ONLY 12 VDC AND 24

VDC THE BATTERY SYSTEM CAN STILL PRESENT A RISK. THE

CURRENT CAPABILITY OF A BATTERY IS SUFFICENT TO BURN WIRE

OR TOOLS VERY RAPIDLY, PRODUCING MOLTEN METAL. OBSERVE

THESE PRECAUTIONS WHEN REPLACING THE BATTERIES:

1. REMOVE WATCHES, RINGS, OR OTHER METAL OBJECTS;

2. USE HAND TOOLS WITH INSULATED HANDLES;

3. DO NOT LAY TOOLS OR OTHER METAL PARTS ON TOP OF

BATTERIES

REPLACE BATTERIES WITH THE SAME NUMBER AND TYPE AS

ORIGINALLY INSTALLED IN THE UPS. THESE BATTERIES HAVE

PRESSURE OPERATED VENTS.

CAUTION:

DO NOT DISPOSE OF BATTERIES IN A FIRE. THE BATTERIES MAY

EXPLODE.

.

4. Connect the new battery in place of the old one, ensuring that  black wire is connected to

the negative (-) terminal and the  red wire is connected to the positive (+) terminal. Small

sparks at the battery connection are normal.

5. Place the new battery in the case taking care not to pinch any wires.

6. Slide the battery door back into its slot and replace the retaining screw.

7. Dispose of the battery properly at an appropriate recycling facility or return it to the supplier

in

the packing material for the new battery. See new battery instructions  for more info.

B

ATTERY 

R

EPLACEMENT 

P

ROCEDURE

PLEASE READ THE CAUTIONS SECTION BEFORE ATTMPTING TO REPLACE

THE BATTERIES

1.  Lay the unit on its side or bring to the edge of a  table.

  Remove the retaining screw holding the

battery door in  place and slide the door towards the

bottom of the unit.

2.  Gently pull out the battery by grasping the battery  removal

tab
3.  Disconnect the two wires connecting the battery to the UPS. Pull back straight on the

connector while wiggling the connector from side to side.

pull

pull

connect

replace

disconnect

En-

glish

7

OBT

AINING SERVICE

I

T

HE 

UPS

 

R

EQUIRES 

S

ERVICE

1.Use the

 TROUBLESHOOTING

 section 5 to eliminate obvious causes.

2.Verify that no circuit breakers are tripped. A tripped circuit breaker is the most common

problem.

3.Call your dealer for assistance. If you cannot reach your dealer, or if he cannot resolve the

problem. call or FAX  Minuteman Technical Support at the following numbers;  Voice

phone

(972) 446-7363, FAX line (972) 446-9011. Please have the following information available

BEFORE calling technical support.

A. Your Name and address.
B. Where and when the unit was purchased.
C. All of the model information on the rear of your Pro Series UPS.
D. Any information on the failure, including LEDs that may be illuminated.
E. A description of the protected equipment, including model numbers if possible.
F.  A technician will ask you for the above information and, if possible, help solve your

    problem over the phone. In the event that the unit requires factory service, the

    technician will issue you a Return Material Authorization Number (RMA #).

  G. If the UPS is under warranty, the repairs will be done at no charge. If not, there will

  be a charge for repair.

4. Pack the UPS in its original packaging. If the original packaging is no longer available, ask
the technical support technician about obtaining a new set.   It is important to pack the UPS
properly in order to avoid damage in transit. Never use Styrofoam beads for a packing
material.

  A. Include a letter with your name, address, day time phone number, RMA number, a

copy of your original sales receipt, and a brief description of the trouble.

5. Mark the RMA # on the outside of all packages. The factory cannot accept any package
without the RMA # marked on the outside.

6. Return the UPS by insured, prepaid carrier to:

Minuteman, Para Systems Inc.

1455 LeMay Drive

Carrollton, Tx. 75007

115 (230) VAC

50 or 60 Hz, +/-0 Hz, unless synchronized to utility during brownout

Simulate sine-wave

Overcurrent and short circuit protected, latching shutdown on overload

8

SPE

CIFICATIONS

3 to 6 years, depending on the number of discharge cycles and ambient temp.

2 to 5 hours from total discharge

<5%

<1%

50 or 60 Hz, autosensing

Resettable circuit breaker

50 or 60 Hz, +/-5%

2 - 4 ms typical

320VA

208W

520VA

338W

680VA

442W

500 J (440J)

19.5 kAmps total

500 J (440J)

39 kAmps total

0 ns (instantaneous) normal mode; <5 ns common mode

<5%

<0.5%

0 to 40 degrees C (+32 to 104 degrees F)

-15 to +45 degrees C (+5 to +113 degrees F)

0 to 95%, non-condensing

0 to +3,000 m (0 to + 10,000 ft)

0 to +15,000 m (0 to +50,000 ft)

IEC 801-2 level IV, 801-4 level IV, 801 -5 level III

<45 dBA

22.2 x 22.8 x 21.6 cm

(8.65 x 9.0 x 8.5 in)

10.2 (11.2) Kg

22.4 (24.7) Lb

7.5 (8.4) Kg

16.4 (18.6) Lb

Listed to UL 1778 Compliance to CSA 22.2

Normal and common mode EMI/RFI suppression

one 12v, 7 Ah

one 12v, 11 Ah

surge protection

let-through (as a percentage of an

a/-6 kV 1.2/50 us, 500

a 8/20 us test)

Telephone line surge protection let-through

(as a percentage of an a/-6 kV 1.2/

50 us, 500 a 8/20 us test

6.9 (8) Kg

15.4 (17.6) Lb

Safety and approvals

EMC Verification

FCC Class B certified

Acceptable input voltage
Input voltage (on-line operation)
Output voltage
Nominal input frequency
Input protection
Frequency limits (on-line operation)
Transfer time
Maximum load

On-battery output voltage
On-battery frequency
On-battery waveshape
Protection
Surge energy rating
(one time, 10/1000 us waveform)
Surge current capability
(one time, 8/20 us waveform)
Surge response time
Surge voltage let-through
(percentage of applied ANSI
C62.41 Cat. A +/-6 V test waveform)
Noise filter
Battery Type-Spill proof, maintenance
free, user replaceable, sealed lead-acid
Typical battery life
Typical recharge time

Operating temperature
Storage temperature (see Section 11)
Operating and storage relative humidity
Operating elevation
Storage elevation
Electromagnetic immunity
Audible noise at 1 m (3 ft.)
Size (H x W x D)

Weight - Net (Shipping)

MBK Series

Date of manufacture

1826

Enabled

Enabled

t

105 VAC (200 for 230

VAC models)

Use this function to uniquely

identify the UPS in your net-

work configuration

Enter the current date when

replacing batteries

When enabled, the UPS will

automatically restart from a

low battery shutdown when

normal A/C returns

Enabled - the UPS will emit

a short beep when in the

battery mode. At Low Bat-

tery  the UPS will emit two

tonesfrom low battery warn-

ing until shutdown.

Disabled - Use only when

software is controlling the

UPS or to silence the alarm

Changes the voltage point at

which the UPS switches to

battery power

(These items require optional software or hardware)

FUNCTION

FACTORY DEFAULT

DESCRIPTION

Up to 64 characters to

define the UPS

Date of battery re-

placement -

day/month/year

XX/XX/XXXX

Up to 5 characters

Enable or disable

Enabled, at low bat-

tery, disabled

98 or 91 VAC (185 or

170 VAC for 230 VAC

models)

USER CHOICES

UPS ID

Battery install

date

Battery life in

days

Enable/

Disable auto

resstart

Set audible

alarm state

Set low voltage

Xfer point

9

At first battery replacement,

reset to reflect actual num-

ber of days experience in

your environment or leave

factory default.

CON

FIGURABLE PARAMETERS

         &  SETTINGS

10

LIMITED PRODUCT WARRANTY

Para Systems Inc. (Para Systems) warrants this equipment, when properly applied and

operated within specified conditions, against faulty materials or workmanship for a period of

three years from the date of manufacture.  For equipment sites within the United States and

Canada,  this warranty covers repair or replacement of defective equipment at the discretion

of Para Systems.  Repair will be from the nearest authorized service center.  Replacement

parts and warranty labor will be borne by Para Systems.  For equipment located outside of

the United States and Canada, Para Systems only covers faulty parts.  Para Systems

products repaired or replaced pursuant to this warranty shall be warranted for the unexpired

portion of the warranty applying to the original product. This warranty applies only to the

original purchaser who must have properly registered the product within 10 days of purchase.

The warranty shall be void if (a) the equipment is damaged by the customer, is

improperly used, is subjected to an adverse operating environment, or is operated outside the

limits of its electrical specifications; (b) the equipment is repaired or modified by anyone other

than Para Systems or Para Systems-approved personnel; or (c) has been used in a manner

contrary to the product’s operating manual or other written instructions.

Any technical advice furnished before or after delivery in regard to use or application of

Para Systems’s equipment is furnished without charge and on the basis that it represents

Para Systems’s best judgment under the circumstances, but it is used at the recipient’s sole

risk.

EXCEPT AS PROVIDED HEREIN, PARA SYSTEMS MAKES NO WARRANTIES,

EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY AND

FITNESS FOR A PARTICULAR PURPOSE. Some states do not permit limitation of implied

warranties; therefore, the aforesaid limitation(s) may not apply to the purchaser.

EXCEPT AS PROVIDED ABOVE, IN NO EVENT WILL PARA SYSTEMS BE LIABLE

FOR DIRECT, INDIRECT, SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES

ARISING OUT OF THE USE OF THIS PRODUCT, EVEN IF ADVISED OF THE POSSIBIL-

ITY OF SUCH DAMAGE. Specifically, Para Systems is not liable for any costs, such as lost

profits or revenue, loss of equipment, loss of use of equipment, loss of software, loss of data,

cost of substitutes, claims by third parties, or otherwise. The sole and exclusive remedy for

breach of any warranty, expressed or implied, concerning Para Systems’s products and the

only obligation of Para Systems hereunder, shall be the repair or replacement of defective

equipment, components, or parts; or, at Para Systems’s option, refund of the purchase price

or substitution with an equivalent replacement product. This warranty gives you specific legal

rights and you may also have other rights which vary from state to state.

Longer term and F.O.B. job site warranties are available at extra cost.  Contact Para

Systems (1-972-446-7363) for details.

LIMI

TED PRODUCT WARRANTY

www.minuteman-ups.com

1455 LeMay Dr.

Carrollton, Texas 75007

Phone: (972) 446-7363

Fax (972) 446-9011

PN: 34000123  rev 1

  NOTE: 230VAC Specs Shown In ( )                 300 VA                    320VA                   520VA                         680VA

300VA

195W

one 12v, 4.5 Ah

17.1 x 17.1 x 16.5 cm

(6.75 x 6.75 x 6.5 in)

4.7 (5.2) Kg

10.1 (11.4) Lb

DECLARATION OF CONFORMITY

 Application of Council Directive(s):

 89/336/EEC, 7/23/EEC                                    

 

 

 Standard(s) to which Conformity is declared:

 EN50091-2, EN60555-2, EN61000-3,         

 

 

   EN50091-1                                                     

 

 

 Manufacturer’s Name:

Para Systems, Inc.      (Minuteman Power Supplies)  

 

 

 Manufacturer’s Address:

1455 LeMay Drive                                                      

 

 

Carrollton, Texas 75007  USA                                    

 

 

 Type of Equipment: Uninterruptible Power Supplies                                                

 

 

 Model No: 

MBK 300YYY, MBK 320YYY, MBK 520YYY, MBK 680YYY

,            

 

 

 Year of Manufacture: Beginning September 1, 1998                                                

 

 

I, the undersigned, hereby declare that the equipment specified above

conforms to the above Directive(s).

 Place: Carrollton, Tx  USA    

            

 

 

Shawn Delavar

          

(Signature)

 Date: September 1, 1998        

            Shawn Delavar            

 

 

 

 

(Full Name)

Regulatory Compliance Engineer

 

 

(Position)