BATTERY REPLACEMENT PROCEDURE

PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING
TO REPLACE THE BATTERY MODULES

The battery modules in the Battery Packs can be replaced without powering down
the whole UPS system.
1.

Turn off all of the DC breakers on the rear panel of all of the Battery Packs.

2.

Remove the retaining screw from the battery cable strain relief on the rear panel
of the UPS and the Battery Packs.

3.

Disconnect all of the external battery cables.

4.

Remove the Battery Pack's cover screws.

5.

Remove the cover and set it aside.

6.

Press down to unlock the battery connector holders on the right hand side of
the Battery Pack and on the left hand side of the Battery Pack. (FIG. 1)

7.

Disconnect the battery connectors (red and black) from each of the battery
modules one on the right hand side of the Battery Pack and one on the left hand
side of the Battery Pack. (FIG. 1)

8.

Remove the fastners from the battery retaining brackets on the right hand side
of the Battery Pack and on the left hand side of the Battery Pack. (FIG. 2)

9.

Remove the battery retaining brackets.

10. Grasp one of the battery module and gently pull it out of the Battery Pack and

set it aside.

11. Grasp the other battery module and gently pull it of the Battery Pack and set it

aside.

NOTE:  

Use Caution, the battery modules are heavy.

12. Slide the new battery modules into the Battery Pack.
13. Re-install all of the battery retaining brackets.
14. Re-install all of the fastners for the battery retaining brackets.
15. Verify proper polarity.  Reconnect all of the battery connectors (red and black)

together.

NOTE:  

Some sparking may occur this is normal.

16. Relock all of the battery connector holders.
17. Re-install the cover.
18. Re-install the cover screws.
19. Reconnect all of the external battery cables.
20. Re-install the retaining screws for all of the battery cable strain reliefs.
21. Turn on all of the DC breakers on the rear panel of all of the Battery Packs.
22. Properly dispose of the old batteries at an appropriate recycling facility or re-

turn them to the supplier in the packing material for the new batteries.

23. The Battery Pack is ready for normal operation.

NOTE:

  If the UPS has a Weak/Bad Battery Alarm after replacing the battery mod-

ules, the user must initiate a self test to clear the Weak/Bad Battery Alarm.  To
initiate a self test see section 4 "

USER INVOKED BATTERY TEST

" in the UPS's

User's Manual.

BP72XL

BP24XL

BP48XL

Chapter 5:  Replacing the Battery

Internal Battery
Module Part #

BM0079

BM0080

BM0081

Model #

WARNING!

  This Battery Pack contains potentially hazardous voltages.  Do

not attempt to disassemble the Battery Pack beyond the battery replacement
procedure.  This Battery Pack contains no user serviceable parts.

CAUTION:

  Do not open or mutilate batteries.  Released electrolyte is harmful

to the skin and eyes and may be toxic.

CAUTION:

  Do not dispose of batteries in a fire.  The batteries may explode.

The batteries in this Battery Pack are recyclable.  Dispose of the batteries
properly.  The batteries contain lead and pose a hazard to the environment
and human health if not disposed of properly.  Refer to local codes for proper
disposal requirements or return the battery to the supplier.

CAUTION:

  The battery system can present a risk of electrical shock.  These

batteries produce sufficient current to burn wire or tools very rapidly, produc-
ing molten metal.  Observe these precautions when replacing the batteries:
1. Remove watches, rings, or other metal objects.
2. Use hand tools with insulated handles.
3. Wear protective eye gear (goggles), rubber gloves and boots.
4. Do not lay tools or other metal parts on top of batteries.
5. Disconnect the charging source prior to connecting or disconnecting the

battery terminals.

6. Determine if the battery is inadvertently grounded.  If the battery is, remove

the source of the grounding.  Contact with any part of a grounded battery
can result in an electrical shock.  The likelihood of such shock will be redu-
ced, if such grounds are removed during installation and maintenance.

Please read all of the 

WARNINGS

 and 

CAUTIONS

 before attempting to ser-

vice the batteries.

 

 Typical battery life is 3 to 5 years.  Environmental factors

do affect battery life.  High temperatures, poor utility power, and frequent,
short duration discharges have a negative impact on battery life.

CAUTION:

 Replace batteries with the same number and type as originally

installed in the Battery Pack.  These batteries have pressure operated vents.
These Battery Packs contain sealed non-spillable maintenance-free lead acid
batteries.

QUALIFIED SERVICE PERSONNEL ONLY

QUALIFIED SERVICE PERSONNEL ONLY

Summary of Contents for BP24XL

Page 1: ...Para Systems Inc 1455 Lemay Dr Carrollton TX 75007 Phone 1 972 446 7363 Fax 1 972 446 9011 Internet minutemanups com UPS Sizing sizemyups com P N 34000532 R1 User s Manual Encompass BPXL Battery Packs...

Page 2: ...1 1 Introduction 2 2 Rear Panel 6 3 Installation 7 4 Obtaining Service 11 5 Replacing the Battery 12 6 Specifications 16 7 Limited Product Warranty 17 A1 Declaration of Conformity 18 Table Of Contents...

Page 3: ...E INSTRUCTIONS CONSIGNES DE S CURIT IMPORTANTES SAUVEGARDEZ CES CONSIGNES Veuillez lire ce manuel avant l installation de l onduleur mod les BP24XL BP48XL BP72XL Il contient de l information important...

Page 4: ...ons unless it receives in writing assurances satisfac tory to us that a the risks of injury or damage have been minimized b the customer assumes all such risks and c our liability is adequately protec...

Page 5: ...years Environmental factors do affect battery life High temperatures poor utility power and frequent short duration discharges have a negative impact on battery life INSTALLATION Be sure to read the i...

Page 6: ...s the battery positive and the black connector is the battery negative 7 Connect the external battery cable from the Battery Pack to the external battery connector on the UPS and secure the strain rel...

Page 7: ...ot under warranty there will be a charge for the repair 4 Pack the unit in its original packaging If the original packaging is no lon ger available ask the Technical Support Representative about obtai...

Page 8: ...r replacing the battery mod ules the user must initiate a self test to clear the Weak Bad Battery Alarm To initiate a self test see section 4 USER INVOKED BATTERY TEST in the UPS s User s Manual BP72X...

Page 9: ...14 15 FIG 1 FIG 2...

Page 10: ...AL DAMAGES ARISING OUT OF THE USE OF THIS PRODUCT EVEN IFADVISED OF THE POSSI BILITY OF SUCH DAMAGE Specifically Para Systems is not liable for any costs such as labor for on site installation on site...

Page 11: ...ies UPS Model No BP24XL BP48XL BP72XL I hereby declare that the equipment specified above conforms to the above Directive s Place Carrollton Texas USA Date September 3 2018 Robert Calhoun Name Manager...

Reviews: