Minco TT859 Installation And Operating Instructions Manual Download Page 7

 

 

 

 

Minco 

Tel: 763. 571.3121  •  Fax: 763. 571.0927  •  www.minco.com 

 

Zero Switch Settings

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

Table 1

 

 

Span Switch Settings

 

 

(Upper Minus Lower Temperature Limits)

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Table 2 

 
      * Span = Upper - Lower Temperature.                 Zero ranges overlap next adjacent range. 

SPAN *

Switch Settings

Center Point

5

6

7

8

°F

°C

ON

ON

ON

ON

31

17

ON

ON

ON

OFF

40

22

ON

ON

OFF

ON

47

26

ON

ON

OFF

OFF

56

31

ON

OFF

ON

ON

65

36

ON

OFF

ON

OFF

74

41

ON

OFF

OFF

ON

81

45

ON

OFF

OFF

OFF

90

50

OFF

ON

ON

ON

99

55

OFF

ON

ON

OFF

106

59

OFF

ON

OFF

ON

115

64

OFF

ON

OFF

OFF

122

68

OFF

OFF

ON

ON

131

73

OFF

OFF

ON

OFF

139

77

OFF

OFF

OFF

ON

148

82

OFF

OFF

OFF

OFF

155

86

 

ZERO

Switch Settings

Center Point

1

2

3

4

°F

°C

ON

ON

ON

ON

-13

-25

ON

ON

ON

OFF

-8

-22

ON

ON

OFF

ON

-2

-19

ON

ON

OFF

OFF

3

-16

ON

OFF

ON

ON

9

-13

ON

OFF

ON

OFF

12

-11

ON

OFF

OFF

ON

18

-8

ON

OFF

OFF

OFF

25

-4

OFF

ON

ON

ON

28

-2

OFF

ON

ON

OFF

34

1

OFF

ON

OFF

ON

39

4

OFF

ON

OFF

OFF

45

7

OFF

OFF

ON

ON

50

10

OFF

OFF

ON

OFF

55

13

OFF

OFF

OFF

ON

61

16

OFF

OFF

OFF

OFF

66

19

 

Summary of Contents for TT859

Page 1: ...Tel 763 571 3121 Fax 763 571 0927 www minco com TT859 TemptranTM 2 wire Temperature Transmitter for RTD Thermometers Installation and Operating Instructions...

Page 2: ...4 to 20 mA DC current The current changes according to the range in which the Temptran is calibrated 4 mA at the lowest temperature of the range rising to 20 mA at the top of the range The leads that...

Page 3: ...cts 0 01 Span F 0 018 Span C Warm up Drift 0 1 of span max assuming Vsupply 24 VDC and Rloop 250 ohms Stable within 15 minutes Supply Voltage 9 4 to 35 volts DC non polarized Input Voltage Effect 0 00...

Page 4: ...or non polar hook up so polarity is not important If calibration is necessary set dip switches before assembling housing See Transmitter Ranging section Connect a DC source not exceeding 35 VDC to the...

Page 5: ...esponding to the lower temperature and verify that the milliammeter still reads 4 0 mA 0 016 mA Correct if necessary then repeat steps 4 and 5 Transmitter Ranging The transmitter is initially calibrat...

Page 6: ...ent adjustments the switch settings should then be changed In the above example if the Zero trim pot cannot adjust the transmitter current down to 4mA with the 30 F Zero switch settings then the Zero...

Page 7: ...74 41 ON OFF OFF ON 81 45 ON OFF OFF OFF 90 50 OFF ON ON ON 99 55 OFF ON ON OFF 106 59 OFF ON OFF ON 115 64 OFF ON OFF OFF 122 68 OFF OFF ON ON 131 73 OFF OFF ON OFF 139 77 OFF OFF OFF ON 148 82 OFF...

Page 8: ...7 45 1328 03 1338 61 1349 18 200 PW 1350 38 1360 64 1370 90 PF 1359 74 1370 30 1380 84 Temp C Sensor 0 2 4 6 8 10 12 14 16 18 20 PW 923 55 915 88 908 20 900 52 PF 921 60 913 73 905 86 897 99 0 PW 1000...

Page 9: ...to 60 C S 0 to100 F 18 to 38 C A 20 to120 F 7 to49 C BI 30 to130 F 1 to54 C N 32 to122 F 0 to50 C H 40 to90 F 4 to32 C SX Special range as defined on job order must fall within adjustment limits of T...

Page 10: ...exclusive remedy available to the buyer in the event of a breach by the seller Items that show evidence of mishandling or misapplication may be returned by the seller at the customer s expense Further...

Page 11: ...et Service Minneapolis MN Tel 1 763 571 3123 Commercial Z I 55432 Fax 1 763 571 0942 09310 Aston France USA custserv minco com Tel 33 5 61 03 24 01 Tel 1 763 571 3121 www minco com Fax 33 5 61 03 24...

Reviews: