Minco TI334 Installation And Operation Instructions Manual Download Page 7

Minco TI334 

 

Tel:  1-763-571-3121 

 Fax:  1-763-571-0927 

 

www.minco.com

6

Troubleshooting

Symptom

Possible cause

Check

Action Required

No display on
the meter

Current loop wiring is
miswired or broken, or
power supply is not on

Check wiring and power supply. Check for the
necessary 2.6 to 2.8 VDC across meter terminals 1
and 2.

Repair wires

Temperature sensor
does not match the
type which the
transmitter requires

Check for the correct temperature sensor type

Replace with correct
temperature sensor

Temperature of the
temperature sensor
may be higher or lower
than the Temptran

TM

transmitter's
temperature range

Verify the sensor’s operating temperature and that
this temperature is within the range of the
transmitter

Replace transmitter with a
range suitable for the
temperatures; recalibrate
meter to match new range

Wiring flaw in the
current loop

Check wires of the 4-20 mA loop

Repair wires

Wiring flaw to the
temperature sensor

Check wires between sensor and transmitter

Repair wires

Meter display
is higher or
lower than
expected and
the reading is
steady

Temperature sensor
may be burned out

Examine the temperature sensor and wires for
damage.

Disconnect sensor from transmitter and ohm the
RTD; 100 ohm Platinum RTD’s are about 110 ohms
at room temperature and 1000 ohm Platinum RTD’s
are about 1100 ohms at room temperature.

Replace bad sensor

1     

displayed

Valid or invalid loop
current signal causing
meter reading to
exceed maximum of
+1999

Figure out what should be displayed based on meter
setup and current flowing in loop. Check for open or
shorted temperature sensor.

An open temperature sensor will not necessarily
cause an overrange display of “

1     

”; for example,

when you have set the meter for a 0 to 500 °F
display, but a wiring problem causes the transmitter
to put out its overrange signal of 25 mA, the meter
will display about "656."

If loop current is correct,
adjust meter range.

If meter range is correct, fix
condition causing too high a
loop current.

-1     

displayed

Valid or invalid loop
current signal causing
meter reading to be
below minimum of
-1999

Figure out what should be displayed based on meter
setup and current flowing in loop.

When wiring to an RTD temperature sensor is
accidentally shorted it causes the Temptran to
produce a current between 3 and 4 mA.  For
example, when you have set the meter for a 0 to
500 °F display, it may give a reading like "-25" for a
3 mA current, not a “

-1      

.”

If loop current is correct,
adjust meter range.

If meter range is correct, fix
condition causing too low a
loop current.

Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Summary of Contents for TI334

Page 1: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Page 2: ...MODEL TI334 Current Loop Meter Installation and Operation Instructions Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com...

Page 3: ...anywhere from the control room to the sensing location Wire it into the current loop anywhere observing the polarity of the loop Remove screws which hold the front cover in place Pull terminal block o...

Page 4: ...ting the meter to the same range perform steps 1 and 4 7 only Procedure 1 Hook up the equipment as shown in the Figure 2 Pull terminal block off from PC board screw wires onto block then re plug block...

Page 5: ...ansmitter Example If your span 20mA temperature is 200 F and your zero temperature 4mA is 100 F then the Span Reading value is 200 F 100 F 300 F Per Table 2 below the appropriate switch settings are t...

Page 6: ...h settings to correspond to your desired temperature range as described in Method 1 steps 2 and 3 3 Set the calibrator to output 4 000 mA 4 Adjust the meter s Zero potentiometer Fig 3 until the meter...

Page 7: ...00 ohm Platinum RTD s are about 110 ohms at room temperature and 1000 ohm Platinum RTD s are about 1100 ohms at room temperature Replace bad sensor 1 displayed Valid or invalid loop current signal cau...

Page 8: ...of any other obligations or liability of the seller or its employees or agents Model Code TI334 Model Number TI334 Polycarbonate NEMA 4X case 25 200 Temperature Range Specify temperature range in eit...

Page 9: ...MINCO 2 950 74 9 2 930 74 4 4 950 125 7 TRANSPARENT COVER HOUSING Temperature Meter Range Switches Zero Span www minco com KNOCKOUT 6 Artisan Technology Group Quality Instrumentation Guaranteed 888 8...

Page 10: ...service in house repair center WE BUY USED EQUIPMENT Sell your excess underutilized and idle used equipment We also offer credit for buy backs and trade ins www artisantg com WeBuyEquipment REMOTE IN...

Reviews: