4-15. Electrical Service Guide
Failure to follow these electrical service guide recommendations could create an electric shock or fire hazard. These recommenda-
tions are for a dedicated circuit sized for the rated output and duty cycle of the welding power source.
In dedicated circuit installations, the National Electrical Code (NEC) allows the receptacle or conductor rating to be less than the rating
of the circuit protection device. All components of the circuit must be physically compatible. See NEC articles 210.21, 630.11, and
630.12.
Three-Phase, 50/60 Hz
Three-Phase, 60 Hz
Input Voltage (V)
380
400
415
500
460
575
Input Amperes (A) At Rated Output
149
141
136
113
123
98
Max Recommended Standard Fuse Rating In Amperes
1
Time-Delay Fuses
2
175
175
150
125
150
110
Normal Operating Fuses 3
225
200
200
175
175
150
Min Input Conductor Size In AWG 4
1/0
1/0
1/0
2
1
3
Max Recommended Input Conductor Length In Feet
(Meters)
398 (121)
441 (134)
474 (145)
490 (149)
482 (147)
548 (167)
Min Grounding Conductor Size In AWG 4
4
6
6
6
6
6
Reference: 2011 National Electrical Code (NEC) (including article 630)
1 If a circuit breaker is used in place of a fuse, choose a circuit breaker with time-current curves comparable to the recommended fuse.
2 “Time-Delay” fuses are UL class “RK5” . See UL 248.
3 “Normal Operating” (general purpose - no intentional delay) fuses are UL class “K5” (up to and including 60 amps), and UL class “H” ( 65 amps and
above).
4 Conductor data in this section specifies conductor size (excluding flexible cord or cable) between the panelboard and the equipment per NEC Table
310.15(B)(16). If a flexible cord or cable is used, minimum conductor size may increase. See NEC Table 400.5(A) for flexible cord and cable
requirements.
Notes
Work like a Pro!
Pros weld and cut
safely. Read the
safety rules at
the beginning
of this manual.
Summary of Contents for Summit Arc 1000
Page 14: ...OM 2221 Page 10 ...
Page 41: ...OM 2221 Page 37 224 360 B ...
Page 42: ...OM 2221 Page 38 Figure 8 2 Circuit Diagram For 400 VAC Input Models ...
Page 43: ...OM 2221 Page 39 224 361 B ...
Page 49: ...Notes ...
Page 50: ...TM 216 869 Page 46 Dynasty 350 700 Maxstar 350 700 Notes ...