Miller-Leaman TOWER GUARD TGSS-20T Owner'S Manual Download Page 7

 

 

Installation Guidelines and Procedures 

Please carefully read the following procedures and guidelines for your system.  Implementing these procedures and 
guidelines will prepare your TowerGuard Filter System for operation.

 

 

Installation and Anchoring 

 

1.  The 

TowerGuard 

Series filter system has been designed to be easily lifted from under the frame.  If lifting straps 

are used, place them underneath the frame, positioned so they do not come in contact with any of the filter 
components.  NEVER lift the system via any of the filter components.   

 

2.  The 

TowerGuard 

Series filter is designed for side-stream use only.  The inlet to the system should draw from a 

non-pressurized location, such as a cooling tower sump.  This system should NEVER be installed in a 
pressurized and/or full-flow application. 

 

3.  Each 

TowerGuard 

contains four anchor points.  The system should be placed on a firm, supporting level surface 

and securely anchored.  Miller-Leaman recommends that a concrete pad be poured for the filter frame to rest on.   

Piping and Connections 

 

1.  The TGSS-20T and TGSS-24T inch 

TowerGuards 

should be plumbed with 2” piping, and the TGSS-30T inch 

with 2-1/2 inch piping.   Reducing the piping size may result in loss of flow.  Make sure to support all piping to 
and from the filter to eliminate stress on the filter components. 

 

2.  Manual valves should be installed in each line to allow the system to be isolated for maintenance.  However, the 

user must make sure that all valves are open prior to running the system.  It is also recommended that unions be 
installed on each connection to allow for easier maintenance should the system ever have to be disconnected 
completely. 

 

3.  Connect the influent line from the sump to the pump.  If the water level is below the pump inlet, a check valve or 

foot valve should be installed.  The water inlet line should NOT exceed 10 PSI. 

 

4.  Connect the effluent line from the system outlet back to the cooling tower sump (or to sweeper piping).    
       This line should not connect into a pressurized line.   

 

5.  Connect the backflush line from the port labeled “Backflush” to a drain.  Do not place any valve or restriction in 

this line and make sure this line drains to a non-pressurized location.  Be sure the drain is capable of handling 
the backflush flow rate.  If not, a reservoir tank may be installed to collect the backflush water and allow it to 
slowly drain out.   

       Insure the backflush water is properly disposed and meets all local code requirements. 
 

Summary of Contents for TOWER GUARD TGSS-20T

Page 1: ...OWNER S MANUAL Operation and Maintenance Guide TGSS 20T TGSS 24T and TGSS 30T...

Page 2: ...n any form mechanical electronic Internet or in any form without the written permission of Miller Leaman Inc Toll Free 800 881 0320 Phone 386 248 0500 Fax 386 248 3033 E mail sales millerleaman com We...

Page 3: ...ny questions concerning the system please contact our application specialists at 386 248 0500 or e mail us at sales millerleaman com The MAXIM Controller also contains a serial number to ID the softwa...

Page 4: ...ct damage may occur Your filter was designed for specific applications It should not be modified and or used for any application other than originally specified If there are any questions regarding it...

Page 5: ...the TowerGuard systems come in multiple sizes depend ing upon the desired flow rate Introduction to TowerGuard Automatic Filtration System Components Frame Skid The T304 stainless steel welded frame s...

Page 6: ...ush timer or manually by the user Backflush Once a backflush is initiated the pump will turn off while the valves rotate to the backflush position When the valves are in the backflush position the pum...

Page 7: ...30T inch with 2 1 2 inch piping Reducing the piping size may result in loss of flow Make sure to support all piping to and from the filter to eliminate stress on the filter components 2 Manual valves...

Page 8: ...sand media bed depth which shall extend to an approximate level below the top of the hydraulic distribution lenses See Figure 1 4 For TGSS 20T and TGSS 24T inch Sand Filter models Remove the top diffu...

Page 9: ...PSI and Maximum flow are listed on this label These must be adhered to during start up 9 Using the pump starter HOA switch momentarily bump start the motor by switching to HAND position only long eno...

Page 10: ...s are factory preset at average values and do not necessarily reflect the individual needs for your system Below are recommendations on how to adjust the controller to fit your system s needs 1 The Pr...

Page 11: ...e all of the union couplings The O rings should be lubricated with silicon gasket grease to prevent them from drying and cracking Check all of the 3 way valves to make sure they are operating properly...

Page 12: ...12 Figure 5 TowerGuard Sand Filter Vessel Parts List TowerGuard Side Mount Sand Filter...

Page 13: ...120 volts AC or 12 volts DC Additional connections to the Outputs should be made to the corresponding Output and a Common ter minal on the circuit board The Pressure Differential Gauge and Timer ON En...

Page 14: ...ves pump starter etc Note Any Common connection may be used for the common negative terminals of the solenoids valves Output 1 Spare Output 2 Backflush valves actuate for backflush flow This output is...

Page 15: ...pump is turned off for the valves to be turned back to the filtration position Status ON Valves to Filtration Screen after the pump has been turned off the valves will be turned back to the filtration...

Page 16: ...rd from screen 8 Company Contact Information screen causes the display to cycle back around to the beginning and display the Screen 1 Status Screen Also pressing the A button to scroll backwards from...

Page 17: ...ting values These values should be adjusted to meet the filters backflush requirements Refer ence the filter manufacturer s owners manual for additional information Backflush Interval The user defined...

Page 18: ...splayed at the beginning of a backflush cycle as the valves are redirecting water from normal flow to backflush flow The controller will automatically turn the pump off while it is changing the valve...

Page 19: ...ime displayed is in hours and min utes This value does not include the elapsed time when the backflush frequency timer is off either when the Status Screen reads Status Off or when the controller is p...

Page 20: ...NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PUR POSE The warranty set forth above is the only warranty applicable to Miller Leaman products Our maximum liability...

Reviews: