22
2. When any switch changes status:
3. When LN model device detects the current over 13A for more than 30s, all switches will close
and upload alarm package:
5.3 Downlink Commands
WS558 supports downlink commands to configure the device. The application port is 85 by
default.
08310060
Channel
Type
Value
08
31 (Switch Status)
Byte 1: 00
Byte 2: 60= 0110 0000
=> L6, L7 open and others close
07c9413f 08310000
Channel
Type
Value
Channel
Type
Value
07
c9 (Current)
41 3f=>3f
41=16193
mA=16.193A
08
31 (Switch
Status)
Byte 1: 00
Byte 2: 00
=>All close
Channel
Type
Description
08
-
Byte 1:
every switch control status per bit,
0=not allow control, 1=allow control
Byte 2:
every switch status per bit, 0=close,
1=open
ff
03 (Set Reporting Interval)
2 Bytes, unit: s
10 (Reboot Device)
ff
32 (Add Delay Task)
Byte 1:
00
Byte 2-3:
delay time, unit: s
Byte 4:
every switch control status per bit,
0=not allow control, 1=allow control
Byte 5:
every switch status per bit, 0=close,
1=open
Note:
WS558 supports adding only one task.
Later command will cover previous command.
23 (Delete Delay Task)
00 ff
26 (Power Consumption)
00-disable, 01-enable