background image

Milbank Manual Transfer Switch Owner’s and Installation Manual

 

15

SET UP

The MMTS monitors power of the selected loads 

connected to the MMTS and displays the power output 

on each Phase using 8 LED’s for each Phase. After the 

MMTS is installed the breakers should be shut off before 

applying power to the MMTS. To test the unit turn on 

the Utility circuit breaker and turn on each load circuit 

breaker.           
Figure 4 show the MMTS circuit breakers set properly 

before turning on the generator. The MMTS is set for a 

10 KW generator at the factory so the LED’s will display 

the load on each phase. When first turned on 3 green 

lights will represent 4 KW on each side. If the load is not 

balanced, within 1 LED on each side, it is recommended 

to redistribute the loads to balance correctly. In between 

LED positions the top most LED will flash, it will flash 

at a slow rate when the represented power is close 

to the lower position and increase in its frequency 

as it approaches the next level. After the MMTS has 

been tested the MTS can be trained to adjust LED’s 

to represent the size of the generator being used. This 

feature is described as Learn Function.                              

Figure 4 – Circuit breaker Setup

On models with a digital meter the LED display shows 

power as a percentage of generator capacity and requires 

the MMTS to be calibrated to the size of the generator 

being used.  To make this calibration the MMTS has a 

“Learn” button and can be set in a few easy steps.  The 

MMTS’ factory default is for a 10,000 watt generator so 

if it is not calibrated to the generator being used it will 

only display 100% when the power passing through the 

switch is at 10kw or 41.6 Amperes.  Setting the capacity 

of the generator is the responsibility of the installer or the 

operator.
There are a few things to keep in mind when using the 

learn function:
     •   The display meter is nonlinear and will display a 

higher resolution when the unit approaches 100%, 

so at the lower levels the LEDs will accumulate at a 

faster rate.

     •   The LEDs on the display represent a percentage 

of the generator capacity and not an actual value 

of power.  In between LED positions the top most 

LED will flash, it will flash at a slow rate when the 

represented power is close to the lower position and 

increase in its frequency as it approaches the next 

level.  When the power reaches the next level it will 

turn solid and the next LED above will begin to flash 

at the slower rate.

     •   When operating on utility power the meter will 

continue to display the percent of power based on 

the calibration that was set for the generator; when 

on utility power it will often display more than 100% 

and this is normal.

     •   The Learn Function measures power on each phase 

of the 240v; each side of the meter represents ½ 

the calibrated capacity of your generator.  To get 

optimal performance from your generator and to 

prevent premature shutdowns, it is important that 

you maintain a balanced load on the circuits in the 

switch.

    •   The Learn Function should only be performed after 

the switch is fully installed and running on generator 

power.  The Learn Function can be rerun at any time 

after installation to calibrate for a different generator 

or to recalibrate to the original generator for better 

performance.

GENERATOR CAPACITY DISPLAY & LEARN FUNCTION: 
(AVAILABLE ON MMTS301SYS & MMTS501SYS)

Summary of Contents for MMTS301

Page 1: ...TALLATION MANUAL Milbank 4801 Deramus Ave Kansas City MO 64120 877 483 5314 milbankworks com MODEL MMTS301SYS MMTS301 MMTS501SYS MMTS501 30 50 AMP MILBANK MANUAL TRANSFER SWITCH Revision 1 1 BOM 11717...

Page 2: ...Moreover because of our continuous product improvement policy we may modify information illustrations and or specifications to explain and or exemplify a product service or maintenance improvement We...

Page 3: ...nts 10 Unpacking and Handling 11 MMTS Wiring Diagram 11 Installation Diagram 12 FUNCTIONAL TESTING 13 Electrical 13 MOUNTING DIMENSIONS 14 SET UP 15 GENERATOR CAPACITY DISPLAY LEARN FUNCTION 15 SETTIN...

Page 4: ...t and should be retained by the owner after the installation has been completed An electronic version can be downloaded at milbankworks com Everyefforthasbeenmadetoensurethattheinformation in this man...

Page 5: ...decisions communicate effectively with your licensed electrician and familiarize yourself with the installation options available The equipment warranty is void unless the system is installed by a lic...

Page 6: ...serious injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate injury NOTICE addresses practices not related to personal injury The manufacturer of this...

Page 7: ...mod r es AVIS pratiques les adresses ne sont pas li s des blessures Le fabricant de ce produit ne peut pas raisonnablement anticiper toutes les circonstances potentielles pouvant comporter un danger...

Page 8: ...ert at all times while working on this equipment Never work on the equipment when you are physically or mentally fatigued If connected devices overheat turn them off and turn off their circuit breaker...

Page 9: ...e vous travaillez sur cet quipement Ne jamais travailler sur l quipement si vous tes fatigu physiquement ou mentalement Si les appareils branch s sont en surchauffe teignez les et mettez leur disjonct...

Page 10: ...X X X X MMTS301SYSL1C X X X X X X X MMTS301SYSL2C X X X X X X X MILBANK 50A MANUAL SWITCH OPTIONS 100A Utility Breaker 50A Generator Breaker 6 Branch Breakers 6 Wiring harness Included 50A Inlet Inst...

Page 11: ...e is NEMA type 3R rated and is suitable for indoor or outdoor installations Guidelines for mounting the unit include Ensure that mounting surface can support the 25 pound weight of the MMTS and adhere...

Page 12: ...lanced on each phase of the generator to achieve optimum generator performance When on generator power the home owner must monitor the loads to prevent stalling the generator due to an overload Change...

Page 13: ...illuminated verify that the circuit has a load attached to the circuit Turn on circuit breaker B2 and verify that the lower right LED is illuminated If the LED is not illuminated verify that the circu...

Page 14: ...14 Milbank Manual Transfer Switch Owner s and Installation Manual MOUNTING DIMENSIONS Figure 3 Mounting Dimensions...

Page 15: ...r being used it will only display 100 when the power passing through the switch is at 10kw or 41 6 Amperes Setting the capacity of the generator is the responsibility of the installer or the operator...

Page 16: ...MTS by shutting off Circuit Breaker A1 B1 2 Turn off all load circuit breakers A2 through B3 and A5 through B6 3 Plug in the portable generator start the generator and turn on A4 B4 4 Turn on Circuit...

Page 17: ...eakers are turned on If the LED s are not balanced then rewire the loads to balance the load on the generator NORMAL OPERATION As each circuit breaker is turned on the LED display should be examined t...

Page 18: ...roved by the manufacturer or registrant of this equipment can void your authority to operate this equipment under Federal Communications Commission rules In order to maintain compliance with FCC regul...

Page 19: ...r return the postcard within 10 days of installation 3 The warranty starts as of the original purchase date by the first retail consumer when the unit is registered if not registered the warranty star...

Page 20: ...T SHOWN 301 COVER PLATE Z1169935 501 COVER PLATE Z1169937 FRONT HINGE SCREWS Z1000062 RISER TO BACK SCREW Z1000183 DEADFRONT TO BACK SCREW Z1001290 GROUND CONN TO BACK SCREW Z1002772 C B STAB ASSY TO...

Page 21: ...IL GEN UTIL Amperage 30 60 50 100 Phase Single Limited Warranty 4 Years Circuits Partial House 8 circuit s maximum Amps 30 50 Service entrance disconnect YES Maximum Load Current YES Rated AC VoltageA...

Page 22: ...A near max Phase A near max both phases are using more power than generator can provide both phases are using more power than generator can provide Try to move some loads from A B to Balance the Gener...

Page 23: ...he lights they will start to dim or flicker when the generator is over capacity Q The GFCI trips on the Generator every time I switch to it A Your generator needs to be converted from portable mode to...

Page 24: ...Milbank 4801 Deramus Ave Kansas City MO 64120 877 483 5314 milbankworks com Revision 1 1 BOM 1171740 3 26 15 MILBANK MANUAL TRANSFER SWITCH...

Reviews: