MIKRODEV MP201 PLC Series Hardware Manual Download Page 5

 


 

 

MP211 SERIES – HARDWARE MANUAL 

 

 

 

 

 

 

About Mikrodev 

 

Since  2006,  MIKRODEV  has  been  developing  and  manufacturing  industrial  control  and 

communication  products.  MIKRODEV  serves  the  system  integrators  in  the  public  and 

private sector, OEM and end users. 

 

Our  products  are  manufactured  complying  with  the  quality  standards  required  by  the 

industrial automation industry and the quality of our products are proved on the field for 

many years 

 

MIKRODEV  is  one  of  the  few  companies  in  the  world  that  has  its  own  designed  IEC 

61131-3  compliant  library  for  its  programmable  logic  control  devices.  In  addition,  the 

open,  flexible,  programmable  SCADA  solution  developed  by  MIKRODEV is  also  available 

to customers. 

 

MIKRODEV products' performance and wide range of applications make them possible for 

customers to achieve faster, simplified and cost-effective results. 

 

 

Summary of Contents for MP201 PLC Series

Page 1: ...MP211 HARDWARE MANUAL MP211 PLC Series 10 2017 MIKRODEV_HM_MP211_EN V1 1...

Page 2: ...fications 7 2 INSTALLATION INFORMATION 8 2 1 Rail Installation 8 2 2 Extension Installation 9 3 CONNECTION DIAGRAMS 10 3 1 Supply Connection 10 3 2 Digital Inputs 11 3 3 Digital Outputs 12 3 4 Relay O...

Page 3: ...ower Connection Diagram 10 Figure 5 DIN Connection Diagram 11 Figure 6 DOUT Connection Diagram 12 Figure 7 Relay Connection Diagram 13 Figure 8 Analog Input Connection Diagram 14 Figure 9 Analog Outpu...

Page 4: ...a wide range of applications from process automation to building automation from machine automation to telemetry applications In this document you can find information about the hardware specificatio...

Page 5: ...y the industrial automation industry and the quality of our products are proved on the field for many years MIKRODEV is one of the few companies in the world that has its own designed IEC 61131 3 comp...

Page 6: ...e the device under conditions other than the environmental conditions specified in the Electrical Specifications section humidity dust liquid and temperature etc Removing the warranty label on the pro...

Page 7: ...al Connections 24 System Running LED 7 Rs232 TX RX Connections 25 Error LED 8 RTD Neutral Connections 26 Protocol Data Transfer 9 RTD Connections 27 Antenna Connection 10 Relay Connections 28 SIM Card...

Page 8: ...ut Digital Input 16 Digital Output 8 Analog Input 4 Analog Output 2 Relay Output 4 RTD 2 Enviromental Conditions Operating Temperature 20 60 C Storage Temperature 40 85 C Humidity 5 95 RH Memory Reten...

Page 9: ...elp of the springs behind the device when a lightly force is applied to the lower part the device locates into the DIN rail easily and the montage is completed See 36 A 36 B DIN Rail Demountage To dem...

Page 10: ...211 SERIES HARDWARE MANUAL 2 2 Extension Installation The MP211 product and its extensions are mounted by sliding over the rail in such a way that the connectors correponds Figure 3 Extension Installa...

Page 11: ...10 MP211 SERIES HARDWARE MANUAL 3 CONNECTION DIAGRAMS 3 1 Supply Connection Supply 12 36 VDC Protected Power 13 W Figure 4 Power Connection Diagram...

Page 12: ...le Input 16 Sink Voltage Range 0 30 VDC ON Voltage Level 7 VDC 30 VDC OFF Voltage Level 0 4 VDC Input Impedance 2M Isolation Optical OFF to ON Response 20 us ON to OFF Response 90 us Fast Counter Inpu...

Page 13: ...utputs Module Output Mosfet Output Voltage Range 0 40 VDC Max Output Current 2 A point 30V Isolation Optical External Voltage Input 3 3 40 VDC Fast Outputs PWM PTO DQ1 DQ2 DQ3 DQ4 Fast Outputs Max Fre...

Page 14: ...elay Outputs Module Output 4 Relay Contact Outputs COM NO Normally Open Contact Max Current 3A 250VAC 3A 30VDC Isolation Potential of relay contacts are isolated from power source and inputs Dry Conta...

Page 15: ...SERIES HARDWARE MANUAL 3 5 Analog Inputs Current Input Count 4 Current Input Type Current 0 20 mA Current Input Precision 1 Precision Common Input GND 1 4 point common Figure 8 Analog Input Connection...

Page 16: ...IES HARDWARE MANUAL 3 6 Analog Outputs Current Output Count 2 Current Output Type Current 0 20 mA Current Output Precision 1 Precision Common Output GND 1 2 point common Figure 9 Analog Output Connect...

Page 17: ...16 MP211 SERIES HARDWARE MANUAL 3 7 RTD Inputs RTD Input Count 2 RTD Input Type PT1000 2 wire Temperature Range 50 200 C Common Input GND 1 2 points common Figure 10 RTD Input Connection Diagram...

Page 18: ...8 RS485 SERIAL PORT RS485 port Count 1 Isolation Galvanic Maximum Slave Counts 200 Communication Distance 1000 m Data Bits 7 8 Stop Bits 1 2 Parity None Even Odd Baudrate 300 bps to 200 kbps Figure 1...

Page 19: ...ERIES HARDWARE MANUAL 3 9 RS232 SERIAL PORT RS232 port Count 1 Communication Distance 10 m Data Bits 7 8 Stop Bits 1 2 Parity None Even Odd Baudrate 300 bps to 200 kbps Figure 12 RS232 Input Connectio...

Reviews: