background image

SPECIFICATIONS

INPUT RANGE

select

 any

 range from

0 to 10 Hz min
to 0 to 60 kHz max

INPUT SENSITIVITY

any

 voltage from 50 mV

to 100 V peak

INPUT IMPEDANCE

100 kilohms

OUTPUT RANGE

Voltage

select

 any

 range from

–10 V to +15 V,
10 mA max load
(min span 0.2 V)

Current

select

 any

 range from

0 to 20 mA max
24 V compliance*
(min span 1 mA)

ACCURACY

±0.1% of span

LINEARITY

±0.1% of span

COMMON MODE REJECTION

120 dB, DC to 60 Hz

ISOLATION (ISO OPTION)

Output/Input
>500 megohms

Breakdown Voltage

>1000 VAC rms

BREAKDOWN,
PWR/CIRCUITRY

>1500 VAC rms

OPERATING TEMPERATURE

14°F to 140°F
–10°C to 60°C

TEMPERATURE STABILITY

±0.02% of span/°C max

OPTION P

Pullup resistor to + input

10 kilohms to +5 VDC

Open-circuit voltage

+5 VDC

POWER

115 VAC ±10%,
50 or 60 Hz
(2.5 W max)

230 VAC ±10%,
50 or 60 Hz
(2.5 W max)

(DC Power Option)

12 VDC
(limits 10 VDC to 15 VDC)
(2.5 W max)

24 VDC
(limits 21 VDC to 32 VDC)
(2.5 W max)

Isolation, DC power
supply to input
common: >500 megohms

*

Compliance: The sum of all
voltage drops in the output loop
cannot exceed 24 V at rated
current (1200 ohms @ 20 mA).

Specifications are subject to change without notice.  ©2007  Wilkerson Instrument Co., Inc.           DWG#W101041D  3/07