background image

MM1820, 1821 AND

1824

POTENTIOMETER

INPUT DUAL ALARM

DESCRIPTION

The MM1820 Series Potentiometer Input
Dual Alarms monitor the slide position of a
potentiometer and provide two sets of spdt,
5 A alarm relays with two independently
adjustable setpoints. Each setpoint has a
set of red/green LEDs to indicate alarm
status. When the signal exceeds a
particular setpoint, the relay becomes
energized. To provide a “fail-safe”
operation  (loss of power resulting in
alarm state), select Option R. The module
can be supplied as a HI/HI, HI/LO, or LO/
LO alarm (HI/LO supplied if not specified).

Standard deadband on both alarms is
fixed at 0.5% of span. Option A provides
adjustable deadband of 0.5% to 100%
of span. Option D, latching alarms has no
deadband control. Once the limit has been
reached, the alarm latches and power to
the module must be momentarily interrupted
to reset the alarm.

All Wilkerson products are designed with
RFI filters and lightning protection to reduce
susceptibility to electrical noise and damage
by lightning. They also utilize a stable 1 V
power supply to excite the potentiometer.
Any value potentiometer from 100 ohms to
100 kilohms can be used.

MODEL NUMBERS

These instructions cover the following
setpoint styles:

MM1820

 Potentiometer Input Dual Alarm

(25 turn screwdriver adj)

MM1821

 Potentiometer Input Dual Alarm

(single turn dials)

MM1824

 Potentiometer Input Dual Alarm

(ten turn precision dials)

OPTIONS

These instructions cover the following
options on the MM1820. Options installed
are listed on the label attached to the side
of the module.

H/H, H/L, L/L
H  

High Alarm.

      Alarm occurs on an increasing signal.

L

   Low Alarm.

      Alarm occurs on a decreasing signal.

A   

Provides top-accessed screwdriver

     adjustable deadbands from 0.5% to
     100% of span, instead of the normal
     fixed 0.5% deadbands.

D     

Latching alarms. Reset by momentary

     interruption of line power.

DC Power

 Inverter isolated 12 or 24 VDC

     power.

R

   The Normal condition for the relays is

de-energized.  They energize for alarm
conditions.  Option R (Reverse sense)
reverses this logic (Failsafe).

U

    

All circuit board conformal coated for

     protection against moisture.

CONTROLS

The MM1820, 1821 and 1824 modules
contain two setpoint controls, plus zero and
span adjustments. An additional internal
control adjusts the potentiometer excitation
voltage.

The setpoint controls in the MM1820 are
25-turn blind trimpots. MM1821 and MM1824
contain 1-turn and 10-turn calibrated dials,
respectively.

Modules with adjustable deadband 

(Option

A)

 also contain two deadband controls.

CALIBRATION

Modules are shipped  with ZERO and SPAN
precalibrated. The user needs only adjust
the SETPOINTs and optional DEADBANDs
for the desired levels.

Refer to the instrument's label to determine
your instrument's supply voltage and input
and output ranges. Refer to the "Block
Diagram and Pin Connections" for pin
connections. Connect a potentiometer to
the input as shown.

(Note: When calibrating latching alarms,
Option D, it will be necessary to
momentarily interrupt power to reset the
alarm after each trip.)

To calibrate the alarm setpoints, adjust the
input potentiometer's position to the desired
alarm 1 setpoint. Adjust the SETPOINT 1
control until its LED just turns red

 (ccw for

a high alarm, cw for low).

Change the input potentiometer's position
to the desired alarm 2 setpoint and
similarly adjust the SETPOINT 2 control.

The MM1821 

(single turn dial) 

and MM1824

(10-turn dial)

 may be set using their 0-100%

dials.

Adjust the optional DEADBAND controls for
the desired amount of deadband. Vary the
input signal up and down to check the
levels at which the relay trips and resets.
the setpoint will remain approximately
centered in the middle of the deadband.

If there is a need to recalibrate ZERO and
SPAN, turn the optional DEADBAND
controls fully ccw and proceed as follows:

Set the input potentiometer to the low end
of its travel 

(fully ccw). 

Turn the SETPOINT

1 control fully ccw. Adjust the ZERO control
until the SETPOINT 1 LED just changes
color.

Change the potentiometer to the high end
of its travel 

(fully ccw). 

Turn the SETPOINT

2 control fully ccw. Adjust the SPAN control
until the SETPOINT 2 LED just changes
color.

Repeat until the ZERO and SPAN settings
are both correct.

After adjusting the ZERO and SPAN
controls, the SETPOINT and DEADBAND
controls will need to be reset as described
above.

An internal control adjusts the potentiometer
excitation voltage. It is factory-set and does
not normally need to be adjusted. The
excitation need not be precise as long as
ZERO and SPAN are calibrated as
described above.

If you should need to adjust this voltage,
loosen the four screws at the bottom of
the module and remove its cover. The
excitation control is located on the small
plug-in preamplifier board.

Connect power and monitor the voltage
between pins 2 (+) and 4 (-) with a digital
voltmeter. Adjust the excitation control for
a reading of 1.000 volts.

Reassemble the cover and recalibrate as
described above.

RELAY CONTACT PROTECTION

When inductive loads such as motors,
relays or transformers are switched,
voltage transients may be generated which
exceed the ratings of the relay contacts.
The resulting arcing can quickly destroy the
contacts. 

(Refer to the SPECIFICATIONS

section for the relay contact ratings).

ALARM TYPE

HI/LO

HI/HI

LO/LO

 SETPOINT 1

 HI

  HI

    LO

 SETPOINT 2

  LO

  HI

    LO

1

2

Reviews: