Important:
If the exhaust ducting is to run through
rooms, ceiling space etc. where there
may be great variations in temperature
between the different areas, the
problem of condensation will need to
be addressed. The exhaust ducting will
need to be suitably insulated.
Condensate trap
(optional extra)
In addition to insulating the exhaust
ducting, we recommend that a suitable
condensate trap is also installed to
collect and evaporate any condensate
which may occur. Condensate traps
are available for
C
125 mm or
C
150 mm ducting.
When installing a condensate trap,
ensure that it is positioned vertically
and if possible directly above the
exhaust connection. The arrow on the
housing indicates the direction of
air-flow.
Connection for air extraction
24