In order to ensure safe operation, and to prevent gases given off
by the heating appliances from being drawn back into the room
when the cooker hood and the heater are in operation
simultaneously, an underpressure in the room of 0.04 mbar (4 pa)
is the maximum permissible.
Ventilation can be maintained by air inlets which cannot be
blocked, in windows, doors or outside wall vents, or by other
technical measures, such as ensuring that the cooker hood can
only be switched on when the heating appliance is switched off or
vice versa. A ventilation brick alone is not generally sufficient to
ensure safe ventilation.
The overall ventilation condition of the dwelling must be taken into
account. If in any doubt, the advice of a competent builder or, for
gas a qualified gas fitter (registered with an official gas safety
body in accordance with national safety regulations, GasSafe in
the UK) must be sought.
If the cooker hood is used in recirculation mode, where the air is
directed back into the room in which it is located, operating a
heating appliance which depends on the room air at the same
time is no cause for concern.
Summary of Contents for DA 2620 EXT
Page 16: ...Guide to the appliance 16 ...
Page 34: ...Installation 34 Assembly parts ...
Page 36: ...Installation 36 Appliance dimensions ...
Page 37: ...Installation 37 ...
Page 53: ......
Page 54: ......
Page 56: ...M Nr 10 186 240 00 en GB DA 2660 DA 2690 DA 2620 DA 2660 EXT DA 2690 EXT DA 2620 EXT ...