MNDC Installation Instructions

 

 

Rev: New  Page 2  of  7 

 

Dimensioned drawing showing conduit locations and sizes

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Wire type 

Due to the small size of this box and limited wire bending room, it is required that the super 
flexible type battery cable be utilized. Cobra Cable X-Flex is one approved type of cable. 
Welding cable although not listed for use in residential wiring will also meet the flexibility 
requirement. Wiring for the din rail mount breakers such as 6AWG for PV circuits may be the 
stiff THHN or similar type of wire. 
 

Top view showing three 1” knockouts. The left 
two knockouts fit charge controllers such as the 
Classic, MX60, C-40 and Tristar controllers 

The left side of the 
MNDC chassis has 
three 2” knockouts 
and two ½” 
knockouts. The 2” 
knockouts are 
intended for inverter 
DC cables. If 
installing to a Trace 
or Xantrex SW 
inverter, use a 2” 
offset nipple to 
attach to the SWCB 
conduit box. 
If routing cables 
directly through the 
hole with no 
conduit, make sure a 
plastic grommet is 
installed to avoid 
chafing. 

The bottom surface is normally where the 
battery cables will enter. The 1” knockout can be 
increased in size to accommodate a second 2” 
conduit opening if required. This is one way to 
hook up to a Trace or Xantrex DR Series conduit 
box. 

Summary of Contents for MNDC125

Page 1: ...of the more common possibilities Features Aluminum chassis no rust in the tropics or around salt water Hinged door for easy access to electrical circuits Inverter breaker included 125 175 or 250 amp Din rail for DC circuits such as PV in Chg Cntrl out DC GFP DC loads PV combiner Ground bus bar with 14 poles Six mounting spots for 500 amp 50mV shunt Mounting spot for insulated bus bar for PV negati...

Page 2: ...ire Top view showing three 1 knockouts The left two knockouts fit charge controllers such as the Classic MX60 C 40 and Tristar controllers The left side of the MNDC chassis has three 2 knockouts and two knockouts The 2 knockouts are intended for inverter DC cables If installing to a Trace or Xantrex SW inverter use a 2 offset nipple to attach to the SWCB conduit box If routing cables directly thro...

Page 3: ...m DC ground The ground bus bar is also where DC lightning arrestors get grounded It is advisable to use one of the conduit knockouts to mount a DC lightning arrestor to the MNDC box It is also common to have a DC lightning arrestor out at the PV Panels that are grounded through their own ground rod In dry climates it is advisable to also run a ground wire from the PV panels to the MNDC ground The ...

Page 4: ...he 500 amp 50mV shunt The MNDC does not come with this shunt so you will need to order the shunt Shunt mounted horizontal on bottom dimples Shunt mounted vertical on bottom dimples 5 16 stud for battery negative tie point Battery Positive connections DC positive from the battery bank connects to the lower section of the large DC inverter breaker The lower inverter breaker stud is also the common p...

Page 5: ...ate a wide range of inverter options Cables may also exit the bottom in order to reach an inverter not mounted to the left of the MNDC enclosure Note the 6AWG wire connected to the lower section of the inverter battery breaker This comes from the output breaker from a charge controller The inverter negative shunt connection has the corresponding negative circuit from the charge controller and nega...

Page 6: ...nstall din rail mount breakers Insure the yellow tab snaps into place to secure the breakers Strip wires 3 8 and bend at from end This section is very tight so pay close attention to wire routing Use cable ties to secure wires in a neatly routed bundle Lat the cover plate on a flat scrap wood surface and using a flat screw driver blade and hammer cut the tabs ...

Page 7: ...MNDC Installation Instructions Rev New Page 7 of 7 MNDC fully wired ...

Reviews: