10 | 

P a g e                                                                 1 0 - 3 3 1 - 2   R E V A

 

 

MNChinook 200M Instructions

 

 

Check the blade rotation-

 Once the blades have been fitted and secured to the chassis, ensure that they 

rotate freely. Also take this opportunity to check that all of the blade and hub mounting screws are secure. 
Remember that the blades are SHARP!   

Fit the nose cone-

 The nose cone can now be fitted to the rotor. This is done by aligning the 3 mounting 

holes of the nose cone with those on the rotor hub plate. Use the 3ea M5 x 14mm hex head screws and 3 
flat washers to secure the nose cone in position. Ensure that the nose cone runs concentrically (true) by 
slowly  spinning  the  rotor  by  hand.  Loosening  the  screws  and  adjusting  the  nose  cone  position  should 
correct any misalign

ment or ‘wobble’. Make sure you do not over tighten the screws and crack the nose 

cone (spinner). 

 

Prepare  the  Turbine  Mount-

 To prepare  your tower  / mount bracket,  you  will need to drill a 6.5mm di-

ameter hole into the mast to secure the turbine. This hole should be drilled 18mm from the top of the tower 
/ mount bracket and should be perpendicular to the surface. The hole should penetrate both sides and cross 
the center line of the tubular section (go straight through).   

Install the Transmission Wire-

 When your tower or mount bracket is ready to have the turbine mounted, 

the next stage is to run the wire from the top of the mount to where the electrical controller and batteries will 
be located. Follow the table below to select the correct wire size. This will vary depending on your nominal 
battery voltage and the distance that the cables will be run. Careful selection of the wire size is required. It 
will not only affect the safety of the system, but also the overall efficiency.  A  wire of insufficient size  will 
cause a voltage drop, wasting the power that has been generated. The wire sizes listed below have been 
selected with efficiency and cost in mind, as it is unlikely that your turbine will be running at full capacity 
100%  of  the  time.  If  in  doubt,  consult  your  local  electrical  supplier.  The  wire  should  be  installed  in 
accordance with local electrical regulations and guidelines. If in doubt, use a local electrical contractor to 
complete the wire installation. See "Cable Strain Relief" on 

page 12

Warning: If a wire of insufficient size is used, heat will build up in the wire causing a potential fire 
hazard. Wire capacities quoted below are based upon AWG wire sizes. 

 

 

 

Transmission Distance 

 

Chinook 200M Output Voltage

 

30 Feet 

 

90 Feet 

300 Feet 

12 Volts 

 

8 AWG   

 

6 AWG   

Not Recommended 

24 Volts 

 

12 AWG   

 

8 AWG   

4 AWG   

48 Volts 

14 AWG 

 

12 AWG 

10 AWG 

 

Mount the Chinook 200M Turbine on to the Support Structure- 

Ensure that the previously installed 

power transmission wires are not yet connected to any batteries 

and are ‘shorted’ together. This will prevent 

the turbine from operating during the installation process. Once this has been done, connect the turbine 
output wires to the transmission wires using a terminal block with a minimum rating of 30 Amps. Move the 

Summary of Contents for Chinook 200 Marine

Page 1: ...e clean renewable electricity anywhere the wind blows Available in 12 24 and 48 Volt models Innovative design axial flux alternator using neodymium iron boron magnets Powder coated stamped aluminum ch...

Page 2: ...nook 200M Instructions Contents Disclaimer 3 Introduction 3 Safety Precautions 4 Specifications 5 Package Contents 6 Mechanical Assembly 7 Electrical Installation 11 Turbine Operation 14 Maintenance 1...

Page 3: ...USA by MidNite Solar Inc 17722 67 th AVE NE Arlington WA 98223 PH 360 403 7207 Fax 360 691 6862 www MidniteSolar com Introduction Please read this manual thoroughly before attempting to assemble insta...

Page 4: ...l installation process This will prevent the turbine from spinning up during the installation Never install the turbine upside down or in any orientation other than that depicted on the installa tion...

Page 5: ...INOOK200M Nominal Voltage 12 24V 48V DC Rotor Blades Glass Reinforced Nylon Rotor Diameter 1 Meter 3 28 Feet Rated Wind Velocity 14m s 31 30 mph Rated Output 200 Watts Max Output 250 Watts Start up Wi...

Page 6: ...o come Package Contents Your Chinook 200M Turbine will arrive containing the components shown below If any of the components are missing or damaged please contact your dealer immediately 3 Blades 1 Tu...

Page 7: ...tely 100 hours of normal operation for the bearing seals to Break in and the lubrication to be distributed correctly around the bearing raceways and ball cages During this period you may notice a redu...

Page 8: ...skin Rotor Blade Assembly Take the three rotor blades and rotor hub plate Be careful when handling the blades they may have sharp edges Use a 10mm socket hexagon key and three M6 x 18mm long cap screw...

Page 9: ...spaced equally Fit the Rotor Blade Assembly The assembled and balanced rotor blades can now be fitted to the Chi nook 200M chassis This is done by placing the rotor hub plate against the bearing hous...

Page 10: ...and batteries will be located Follow the table below to select the correct wire size This will vary depending on your nominal battery voltage and the distance that the cables will be run Careful selec...

Page 11: ...e may be different ways of wiring small wind turbines photovoltaic panels charge controllers and batteries together This type of system will often expand organically but the following guidelines shoul...

Page 12: ...inst the buildup of static and lightning strikes The turbine mount should be grounded separately with its own ground rod and an appropriate surge arrestor installed to help prevent damage to the batte...

Page 13: ...ries are fully charged or not Depending on the size of the dump load the turbine may slow down or stall during a period when the power is being diverted Larger capacity battery banks will be able to s...

Page 14: ...acceptable limits the CDL will stop diverting current to the dump load Refer to the CDL controller user manual for specific operating instructions Shut Down By activating the optional stop switch if...

Page 15: ...w set of rotor blades should be installed Contact MidNite Solar for replacements Inspect the roots of the blades attachment tabs for signs of stress cracking or fatigue A new set of rotor blades shoul...

Page 16: ...inook 200M turbine Rotor Blades sold only in sets of 3 Slip Ring Wiper set of 2 Slip Ring sold only with yaw mount assembly Stator 48VDC Stator 24VDC Stator 12VDC Bridge Rectifier Yaw Bearing Housing...

Page 17: ...umber issued by MidNite Solar For an RMA number contact MidNite Solar Inc 17722 67th Ave NE Arlington WA 98223 360 403 7207 Purchasers must prepay all delivery costs or shipping charges to return any...

Reviews: