Specifications & Performances
6. Field wiring
The control line should be shielded wire. Using other wiring shall create signal interference, thus leading to
error operation.
The shielded nets at the two sides of shielded wires are either grounded to the earth, or connected with each
other and jointed to the sheet metal along to the earth.
Control wire could not be bound together with refrigerant pipeline and power wire. When power wire and
control wire is distributed in parallel form, keep gap between them above 300mm so as to preventing signal
interference.
Control wire could not form closed loop.
Control wire has polarity, so be careful when connecting.
6.1 Electric wiring of outdoor/indoor units
Outdoor unit power supply
Indoor unit power supply
6.2 Example for control wire connection