33
If users switch on A/C by remote controller, the compressor will run at the Fmax frequency for 7
minutes according to outdoor ambient temp. During the 7 minutes, frequency limitation is active.
7 minutes later, the compressor running frequency will be controlled as below:
While
Temp.zone
A B
C
D
E
F
G
Frequency
F8 F8
F7
F6
F5
F3
F1
Note:
When T1-Ts keeps in the same temp. zone for 3 minutes, the compressor will run as the below rules:
A~E: Increase the frequency to the higher level until to F8.
F: Keep the current frequency.
G: Decrease the frequency to the lower level until to F1.
H: Run at F1 for 1h.(if T1-Ts<-2 , compressor will stop)
Meanwhile, the compressor running frequency is limited by the current.