Drainage pipe installation
100
Installation
6.2.3 Individual design of drainage pipe system
The drainage pipe of air conditioner shall be installed separately with other sewage pipe, rainwater pipe
and drainage pipe in building.
The drainage pipe of the indoor unit with water pump should be apart from the one without water pump.
6.2.4 Supporter gap of drainage pipe
In general, the supporter gap of the drainage pipe horizontal pipe and vertical pipe is respectively
1m~1.5m and 1.5m~2.0m.
Each vertical pipe shall be equipped with not less than two hangers.
Overlarge hanger gap for horizontal pipe shall create bending, thus leading to air block.
Too long distance
Gas bag
6.2.5 The horizontal pipe layout should avoid converse flow or bad flow
Drainage pipe
Water flow
Drainage pipe
Drainage pipe
Drain
tee
Drain
tee
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Water flow
Drain
tee
Branch pipe
Water flow
Water flow
Keep a certain degree
Branch pipe
Gas
Gas
Main pipe
Main pipe
The correct installation will not cause converse water flow and the slope of the branch pipes can be
adjusted freely
The false installation will cause converse water flow and the slope of the branch pipe can not be
adjusted.
6.2.6 Water storage pipe setting
If the indoor unit has high extra static pressure and without water pump to elevate the condensate water,
such as high extra static pressure duct unit , the water storage pipe should be set to avoid converse flow
or blow water phenomena.
Summary of Contents for U2MRS-12
Page 7: ...Service Space Indoor Units 13 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 13: ...Field Wiring Indoor Units 19 9 Field Wiring...
Page 20: ...Wiring Diagrams 26 Indoor Units 4 Wiring Diagrams 12K 12K 24K 30K 36K...
Page 21: ...Wiring Diagrams Indoor Units 27 MTB 24HWDN1 QRC4...
Page 28: ...Field Wiring 34 Indoor Units 10 Field Wiring 12K 18K 24K 30K 36K...
Page 32: ...Service Space 38 Indoor Units 3 Service Space...
Page 34: ...Wiring Diagrams 40 Indoor Units 36K...
Page 37: ...Indoor Units 43 9 Field Wiring...
Page 40: ...Dimensions 46 Indoor Units 2 Dimensions...
Page 41: ...Service Space Indoor Units 47 3 Service Space...
Page 42: ...Wiring Diagrams 48 Indoor Units 4 Wiring Diagrams 12K 18K...
Page 46: ...52 Indoor Units 10 Field Wiring 12K 18K...
Page 48: ......
Page 51: ...Dimensions Console Type 57 2 Dimensions MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Page 52: ...Service Space 58 Console Type 3 Service Space...
Page 53: ...Wiring Diagrams Console Type 59 4 Wiring Diagrams MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Page 58: ...Field Wiring 64 Console Type 10 Field Wiring MFAU 12HRFN1 QRC8 MFA 16HRFN1 QRC8...
Page 64: ...Wiring Diagrams 70 Outdoor Units 4 Wiring Diagrams U2MRS 12...
Page 65: ...Wiring Diagrams Outdoor Units 71 18K 24K 30K 36K...
Page 66: ...Wiring Diagrams 72 Outdoor Units...
Page 67: ...Wiring Diagrams Outdoor Units 73...
Page 92: ...Refrigerant pipe installation 98 Installation...
Page 123: ...Troubleshooting Electrical Control System 129 2 4 1 2 Outdoor unit malfunction...
Page 130: ...Troubleshooting 136 Electrical Control System 2 4 2 3 Up down panel is not closed...
Page 134: ...Troubleshooting 140 Electrical Control System 2 4 4 3 E3 malfunction...
Page 135: ...Troubleshooting Electrical Control System 141 2 4 4 4 E4 malfunction...
Page 141: ...Troubleshooting Electrical Control System 147 2 4 4 9 P1 malfunction For 36k models...
Page 142: ...Troubleshooting 148 Electrical Control System 2 4 4 10 P2 malfunction For 36k models...
Page 143: ...Troubleshooting Electrical Control System 149 2 4 4 11 P3 malfunction...