Electrical Control Function
Electrical Control System
163
1. Electrical Control Function
1.1 Abbreviation
T1: Indoor room temperature
T2: Middle indoor heat exchanger coil temperature
T2B: Indoor heat exchanger exhaust coil temperature
T3: Outdoor heat exchanger pipe temperature
T4: Outdoor ambient temperature
T5: Compressor discharge temperature
1.2 Main Protection
1.2.1 Compressor Restart Delay
1.2.2 Temperature Protection of Compressor Discharge
When the discharge temperature of compressor rises, the running frequency is limited according to the
following rules:
12K 16~60K
T 5
C o m p r e s s o r o f f
F r e q u e n c y l im it 1
F
E
D
C
F r e q u e n c i e s i n c r e a s e s lo w ly
B
N o r m a l
A
F r e q u e n c y h o ld in g
F r e q u e n c y l im it 2
T 5
C o m p r e s s o r o f f
F r e q u e n c y lim it
N o r m a l
F r e q u e n c y h o l d in g
1.2.3 Indoor Fan Delayed Open Function
When the unit starts up, the louver is immediately active . The indoor fan o pens 7 seconds later.
If the unit runs in heating mode, the indoor fan is also regulated by the anti -cold wind function.
1.2.4 Fan Speed Malfunction
For the console:
If the indoor fan speed is lower than 300 RPM for certain time , the unit stops and the LED displays the failure
code.
For A6 Duct:
If a fault occurs on the air volume regulator or the regulator enters protection mode, it sends the error
message CF and an instruction to reduce fan speed to the master. The message and the instruction can be
inquired with the remote controller or the wired controller. (Fault and protection information are displayed for
one minute). After a fault occurs, the master unit shows the error code E3 and the fault count for one minute.
If the fault occurs three times, then the fan is unable to resolve the problem independently. External
shutdown by a remote controller, wired controller, or central controller must be used to clear the fan fault and
fault count. The fan runs normally for 5 minutes while clearing fault count.
0
:
No malfunction
1
:
P0 Overcurrent
2
:
Overpressure
3
:
Overload
4
:
Over speed
Summary of Contents for Super DC Series
Page 1: ...Contents i Energy Related Products SUPER DC INVERTER SERIES Service Manual 2017...
Page 14: ...Service Space Indoor Units 12 3 Service Space 1000mm 1000mm 1000mm 1000m m Chart 3...
Page 17: ...Air Velocity Distributions Reference Data Indoor Units 15 30 42K Cooling Heating...
Page 18: ...Air Velocity Distributions Reference Data Indoor Units 16 48 55K Cooling Heating...
Page 23: ...Field Wiring Indoor Units 21 10 Field Wiring...
Page 30: ...Wiring Diagrams Indoor Units 28 4 Wiring Diagrams MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0...
Page 32: ...Static Pressure Indoor Units 30 5 Static Pressure MTBU 12HWFN1 QRD0W MTB 18HWFN1 QRD0...
Page 33: ...Static Pressure Indoor Units 31 MTB 24HWFN1 QRD0 MTB 30HWFN1 QRD0...
Page 45: ...Features Indoor Units 43...
Page 53: ...Field Wiring Indoor Units 51 9 Field Wiring...
Page 57: ...Service Space Indoor Units 55 3 Service Space...
Page 67: ...Field Wiring Indoor Units 65 10 Field Wiring...
Page 70: ...Features Indoor Units 68...
Page 72: ...Service Space Indoor Units 70 3 Service Space...
Page 73: ...Wiring Diagrams Indoor Units 71 4 Wiring Diagrams MCA3U 12HRFN1 QRD0W MCA3 18HRFN1 QRD0...
Page 77: ...Field Wiring Indoor Units 75 10 Field Wiring MCA3U 12HRFN1 QRD0W MCA3 18HRFN1 QRD0...
Page 81: ...Features Console Type 79 1 7 Active carbon filter is standard...
Page 83: ...Console Type Console Type 81 3 Service Space...
Page 84: ...Console Type Console Type 82 4 Wiring Diagrams MFAU 12HRFN1 QRC8W MFA 16HRFN1 QRC8W...
Page 89: ...Console Type Console Type 87 10 Field Wiring...
Page 93: ...Service Space M Floor standing Type 91 3 Service Space...
Page 95: ...Wiring Diagrams M Floor standing Type 93 MFM 55ARFN1 RRD0...
Page 101: ...Field Wiring M Floor standing Type 99 MFM 55ARFN1 RRD0...
Page 105: ...Service Space GAFloor standing Type 103 3 Service Space...
Page 106: ...Wiring Diagrams GAFloor standing Type 104 4 Wiring Diagrams MFGA 55ARFN1 RRD0 B...
Page 112: ...Field Wiring GAFloor standing Type 110 10 Field Wiring...
Page 115: ...Dimensions Outdoor Units 113 Model KBtu h Unit mm W D H W1 A B 48 55 952 415 1333 1045 634 404...
Page 117: ...Wiring Diagrams Outdoor Units 115 3 Wiring Diagrams MOB30U 12HFN1 QRD0W MOB30U 16HFN1 QRC8W...
Page 118: ...Wiring Diagrams Outdoor Units 116 MOB30U 18HFN1 QRD0 MOCA30U 24HFN1 QRD0 MOD30U 30HFN1 QRD0...
Page 119: ...Wiring Diagrams Outdoor Units 117 MOD30U 36HFN1 QRD0 MOD30U 42HFN1 QRD0...
Page 120: ...Wiring Diagrams Outdoor Units 118 MOD30U 36HFN1 RRD0 MOD30U 42HFN1 RRD0...
Page 121: ...Wiring Diagrams Outdoor Units 119 MOE30U 48HFN1 QRD0 MOE30U 48HFN1 RRD0 MOE30U 55HFN1 RRD0...
Page 154: ...Refrigerantpipe installation Installation 152...
Page 179: ...Troubleshooting Electrical Control System 177 2 1 8 Display board of GA floor standing...