MIV V4+ Indoor Units
DM12-01.01.02-01en
Four-way Cassette Type MVC-A-VA1
6
Model
MVC90A-VA1 MVC100A-VA1 MVC112A-VA1 MVC140A-VA1
Power supply
V- Ph-Hz
220-240V, 1Ph, 50Hz
Cooling
Capacity
kW
9.0 10.0 11.2 14.0
Input W
160
160
160
170
Rated current
A
0.7
0.7
0.7
0.8
Heating
Capacity
kW
10.0 11.0 12.5 15.0
Input W
160
160
160
170
Rated current
A
0.7
0.7
0.7
0.8
Indoor fan motor
Model
YDK90-6E-1
YDK90-6E-1
YDK90-6E-1
YDK90-6E-1
Type
AC motor
AC motor
AC motor
AC motor
Brand
Welling
Welling Welling Welling
Input W
165/143/114/93
165/143/114/93
165/143/114/93
204/175/140/120
Capacitor uF
3.5
3.5
3.5
4
Speed (hi/mid/lo)
r/min
770/640/550
770/640/550
770/640/550
820/750/620
Indoor coil
Number of rows
2
2
2
2
Tube pitch(a)x row pitch(b)
mm
21x13.37
21x13.37
21x13.37
21x13.37
Fin spacing
mm
1.5
1.5
1.5
1.5
Fin type
Hydrophilic Aluminum
Tube outside dia. and type
mm
Ф
7, Innergroove Tube
Coil length x height x width
mm
1955x252x26.74 1955x252x26.74 1955x252x26.74 1955x252x26.74
Number of circuits
8
8
8
12
Indoor air flow (H/M/L)
m
3
/h 1540/1300/1120 1540/1300/1120 1540/1300/1120 1800/1500/1280
Indoor noise level (Hi/Mid/Lo)
dB(A)
48/45/43
48/45/43
48/45/43
50/47/44
Indoor unit
Dimension (WxHxD)
mm
840x300x840
840x300x840 840x300x840 840x300x840
Packing (WxHxD)
mm
955X317X955
955X317X955
955X317X955
955X317X955
Net/Gross weight
kg
32/37
32/37
32/37
32/37
Panel
Model
T-MBQ-02F1
Dimension (WxHxD)
mm
950x46x950 950x46x950 950x46x950 950x46x950
Packing (WxHxD)
mm
1000x60x1000
1000x60x1000
1000x60x1000
1000x60x1000
Net/Gross weight
kg
6/8
6/8
6/8
6/8
Refrigerant type
R410A
Throttle
Electronical expansive valve
Design pressure
MPa
4.4/2.6
4.4/2.6
4.4/2.6
4.4/2.6
Refrigerant piping Liquid side/ Gas side
mm
Φ
9.52/
Φ
15.9
Φ
9.52/
Φ
15.9
Φ
9.52/
Φ
15.9
Φ
9.52/
Φ
15.9
Connecting wiring
Power wiring
Nb×mm
2
3×2.5(L
≤
20m)
;
3×3.5(L
≤
50m)
Signal wiring
Nb×mm
2
3×0.75 3×0.75 3×0.75 3×0.75
Drainage water pipe dia.
mm
ID
Ф
28.5 OD
Ф
32 ID
Ф
28.5 OD
Ф
32 ID
Ф
28.5 OD
Ф
32 ID
Ф
28.5 OD
Ф
32
Standard Controller
Wireless remote controller (RM05/BG(T)E-A) , to set address
Operation temp
C
17
~
30
Notes:
1.
Nominal cooling capacities are based on the following conditions: return air temp.: 27°CDB, 19°CWB, and outdoor
temp.:35°CDB, equivalent ref. piping: 8m (horizontal)
2.
Nominal heating capacities are based on the following conditions: return air temp.: 20°CDB, outdoor temp.: 7°CDB, 6°CWB,
and equivalent ref. Piping: 8m (horizontal)