To avoid oil accumulation in the outdoor unit, please install the branching pipes properly.
5. Drainage pipe engineering
5.1 Installation essentials
5.1.1
Installation principles
1) Slope; 2) reasonable pipe diameter; 3) nearby discharge
5.1.2
Installation requirements
1. Before installing condensation piping, determine its route and elevation to avoid interference with other
pipes and ensure a smooth slope.
2. Make sure two horizontal condensation pipes not encounter to avoid back flow or other complications.
a. Correct connection:
10°
10°
A
Correct
Wrong
U-shaped branching pipe
Horizontal surface
A direction view