DM17-01.01.08en
Light Commercial R410A on-off
160
Indoor
unit
More than 50mm
More than 25mm
Plug
Water storage pipe
6.2.7 Lifting pipe setting of indoor unit with water pump
The length of lifting pipe should not exceed the pump head of indoor unit water pump.
Pump head of big four way cassette: 750mm
Pump head of compact four way cassette: 500mm
The drainage pipe should be set down inclined after the lifting pipe immediately to avoid wrong
operation of water level switch.
Refer the following picture for installation reference.
Flexible pipe 300mm
Hanger
A
A:Length of horizontal pipe
≤
150mm
B: Lift height
≤
the pump head of water pump
Down incline pipe
B
6.2.8 Blowhole setting
For the concentrated drainage pipe system, there should design a blowhole at the highest point of main
pipe to ensure the condensate water discharge smoothly.
The air outlet shall face down to prevent dirt entering pipe.
Each indoor unit of the system should be installed it.
The installation should be considering the convenience for future cleaning.
Blowhole
Plug
Indoor unit
Plug
Indoor unit
6.2.9 The end of drainage pipe shall not contact with ground directly.
6.3 Drainage test
6.3.1 Water leakage test
After finishing the construction of drainage pipe system, fill the pipe with water and keep it for 24 hours to
check whether there is leakage at joint section.
Summary of Contents for MUE-36HRN1-R1
Page 13: ...Light Commercial R410A on off DM17 01 01 08en 13 Dimensions 3...
Page 14: ...DM17 01 01 08en Light Commercial R410A on off 14 Service Space 4...
Page 22: ...DM17 01 01 08en Light Commercial R410A on off 22 Field Wiring 11...
Page 29: ...Light Commercial R410A on off DM17 01 01 08en 29 4 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 35: ...Light Commercial R410A on off DM17 01 01 08en 35 6 Wiring Diagrams MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Page 36: ...DM17 01 01 08en Light Commercial R410A on off 36 MCD 36HRN1 R1...
Page 37: ...Light Commercial R410A on off DM17 01 01 08en 37 MCD 48HRN1 R MCD 60HRN1 R...
Page 41: ...Light Commercial R410A on off DM17 01 01 08en 41 10 Field Wiring MCD 18HRN1 Q1 MCD 24HRN1 Q1...
Page 42: ...DM17 01 01 08en Light Commercial R410A on off 42 MCD 36HRN1 R1 MCD 48HRN1 R MCD 60HRN1 R...
Page 55: ...Light Commercial R410A on off DM17 01 01 08en 55 6 Wiring Diagrams MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Page 56: ...DM17 01 01 08en Light Commercial R410A on off 56 MTI 36HWN1 R1 MTB 48HWN1 R MTB 60HWN1 R...
Page 63: ...Light Commercial R410A on off DM17 01 01 08en 63 11 Field Wiring MTB 18HWN1 Q1 MTB 24HWN1 Q1...
Page 64: ...DM17 01 01 08en Light Commercial R410A on off 64 MTI 36HWN1 R MTB 48HWN1 R MTB 60HWN1 R...
Page 76: ...DM17 01 01 08en Light Commercial R410A on off 76 6 Wiring Diagrams MHG 24HWN1 Q1...
Page 77: ...Light Commercial R410A on off DM17 01 01 08en 77 MHG 36HWN1 R1...
Page 78: ...DM17 01 01 08en Light Commercial R410A on off 78 MHG 48HWN1 R...
Page 79: ...Light Commercial R410A on off DM17 01 01 08en 79 MHG 60HWN1 R...
Page 84: ...DM17 01 01 08en Light Commercial R410A on off 84 11 Field Wiring MHG 24HWN1 Q1 MHG 36HWN1 R1...
Page 85: ...Light Commercial R410A on off DM17 01 01 08en 85 MHG 48HWN1 R MHG 60HWN1 R...
Page 91: ...Light Commercial R410A on off DM17 01 01 08en 91 4 Service Space...
Page 99: ...Light Commercial R410A on off DM17 01 01 08en 99 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Page 104: ...DM17 01 01 08en Light Commercial R410A on off 104 MUE 36HRN1 R1 MUE 48HRN1 R MUE 60HRN1 R...
Page 110: ...DM17 01 01 08en Light Commercial R410A on off 110 4 Service Space...
Page 112: ...DM17 01 01 08en Light Commercial R410A on off 112 6 Wiring Diagrams MFM 24ARN1 Q...
Page 125: ...Light Commercial R410A on off DM17 01 01 08en 125 MOD31U 36HN1 R MOU 48HN1 R...
Page 126: ...DM17 01 01 08en Light Commercial R410A on off 126 MOUA 60HN1 R...
Page 178: ...DM17 01 01 08en Light Commercial R410A on off 178 2 1 5 Display board of floor standing...