Service manual
35
11.7.6
0
T-Ts
Room temp. up
Room temp. down
2
Med fan
High fan
11.7.7
11.7.8
Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
11.7.9
T
T temp. up
T temp. down
TE7
Compressor on
Fan on
TE8
TE9
Compressor off
Fan off
Compressor on
Fan off
11.7.10
11.7.11
The louver opens to Standard Angle ANGLHEAT when power is on for the first time
11.8
Defrosting mode(available for heating mode)
11.8.1
Defrosting condition: Defrosting starts when either of the following
①
&
②
:
①
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following:
TM def.
TA-TS
TH def.
High fan
Med fan
Low fan
TL def.
Breeze
②
Calculate from the end of latest defrost, evaporator high temp. Protection only closes outdoor fan with the compressor still
running. Add up to 90 minutes.