background image

Service manual 

23 

 

-1

TA-TS

2

Heating (fan only at cooling)

Fan only

Cooling

 

8.10.2 The indoor fan blows automatically in corresponding selected mode

 

8.10.3 The motion of indoor fan’s blade should accord with the selected operation mode

 

8.10.4 One mode should be carried out for at least 15 minutes once selected. If the compressor cannot start for 

15 minutes, reselect the operation mode according to the room temp. and set temp., or reselect when the set 

temp. varies 

 

8.11 Force cooling function 

8.11.1 Select forced cooling function with the forced cooling button or the switch 

8.11.2 The compressor is unconditionally turned on, after 30 minutes cooling operation whose fan mode is set as 

low, the A/C operates at the DRY mode with a set temp. of 24

 

8.11.3 All protections of remote control cooling are available at forced cooling operation 

8.11.4 Forced Auto function 

Select forced auto function with the forced auto button or the switch. 

In forced auto status the A/C operates at remote control mode with a set temp. of 24

 

Manual operation is controlled by touching buttons and divided into force cooling and forced auto mode. It 

transfer between these two modes by pressing the buttons, the cycling order of the button press is as below 

graph show to you. 

Forced 
cooling

Forced 

auto

Remote 

mode

 

 

8.12 Sleep mode 

8.12.1 The sleep function is available at cooling, heating or auto mode 

8.12.2 Cooling:   

The set temperature rise 1

 per hour. Two hours later, the set temperature will maintain as a constant and the 

fan speed is kept at low speed.   

Time

Room temperature

2

1

1'C

1'C

 

8.12.3 Heating: 

Summary of Contents for MSH-21HRN1-QB8

Page 1: ...ce manual Service manual Room airconditioner Room airconditioner Room airconditioner Room airconditioner Split Wall mounted Type Split Wall mounted Type Split Wall mounted Type Split Wall mounted Type...

Page 2: ...12 7 6 Re air purging Re installation 13 7 7 Balance refrigerant of the 2 way 3 way valves 14 7 8 Evacuation 17 7 9 Gas charging 18 8 Electronic function 19 8 1 Proper symbols and their meaning 19 8 2...

Page 3: ...Operation lamp flashes and Timer lamp off 29 10 6 Operation lamp flashes and Timer lamp on 29 10 7 Operation lamp off and Timer lamp flashes 30 10 8 Operation lamp on and Timer lamp flashes B d Nie zd...

Page 4: ...stand It may cause injury accident or damage to the product Be sure the installation area does not deteriorate with age If the base collapses the air conditioner could fall with it causing property da...

Page 5: ...uld cause product malfunction or inefficient operation Operational Do not expose the skin directly to cool air for long periods of time Do not sit in the draft This could harm to your health Do not us...

Page 6: ...ouver direction according to operation mode Two direction air vane The fan is turn to low speed cooling heating The unit will be turn off at the seventh hour Sleep mode auto control The function is us...

Page 7: ...makes the outdoor unit run more quietly Low noise air flow system The hydrophilic fin can improve the heating efficiency at operation mode Hydrophilic aluminum fin It is only operated in the heating...

Page 8: ...ervice manual 5 3 Dimension 3 1 Indoor unit Dimension Mode W H D 21K 1030 313 221 24K 1030 313 221 3 2 Outdoor unit Dimension Mode W H D L1 L2 L3 21K 845 695 335 560 360 560 24K 845 695 335 560 360 56...

Page 9: ...000 1235 1145 1045 m3 h 1000 960 880 1080 1020 960 dB A 47 45 43 48 46 43 Model YDK53 6E YDK100 6C Brand Welling Welling Input W 181 173 Capacitor uF 3 5 Speed r min 840 900 m3 h 2500 2500 dB A 60 62...

Page 10: ...Service manual 7 4 Refrigerant cycle diagram Cooling only Heat pump mode...

Page 11: ...from the continuous operation under constant air temperature conditions However excludes the initial pull down stage 5 2Heating operation Indoor air temp DB Outdoor unit air temp DB Note The chart is...

Page 12: ...Service manual 9 6 Wiring diagram Indoor Outdoor...

Page 13: ...cording to the following specifications sheet Grade Unit 21K 24K mm 2 2 5 2 5 7 3 Pipe length and the elevation Pipe size Capacity Btu h GAS LIQUID Standard length m Max Elevation B m Max Pipe length...

Page 14: ...Check the flare connection for gas leakage Purge the air from the system Set the 2 way valve to the open position and remove the cap from the 3 way valve s service port Using the hexagonal wrench to p...

Page 15: ...e charge hose with the push pin to the gas service port Air purging of the charge hose Open the low pressure valve on the charge set slightly to purge air from the charge hose Set the 2 way valve to t...

Page 16: ...r 1 minutes repeat 3 times After purging the air use a torque wrench to tighten the flare nut to on the 2 way valve Check the gas leakage Check the flare connections for gas leakage Discharge the refr...

Page 17: ...e service port Open the valves Low side on the charge set and discharge the refrigerant until the gauge indicates 0 05 to 0 1 Mpa If there is no air in the refrigeration cycle the pressure when the ai...

Page 18: ...has moved toward 0 1 Mpa 76 cmHg vacuum of 4 mmHg or less Close the valve Low side on the charge set turn off the vacuum pump and confirm that the gauge needle does not move approximately 5 minutes a...

Page 19: ...e specified amount of refrigerant if can be charged with a little at a time approximately 150g each time0 while operating the air conditioner in the cooling cycle however one time is not sufficient wa...

Page 20: ...ature TE6 Evaporator low temperature protection restoring temperature TE7 Evaporator high temperature protection compressor off temperature TE8 Evaporator high temperature protection fan off temperatu...

Page 21: ...in 4 minutes the unit stops and LED displays failure information and can t returns to normal operation automatically 8 4 5 The current protection of the compressor If compressor turns off for continuo...

Page 22: ...Service manual 19...

Page 23: ...Compressor and outdoor fan on Compressor and outdoor fan off after 5 mins 8 7 Dehumidifying mode Indoor fan speed at low speed Protection is same as cooling mode 8 8 Heating mode 8 8 1 Generally the...

Page 24: ...ter can be changed from 0 to 3 8 8 4 Indoor Fan actions at heating mode Indoor Fan can be set at HIGH MID LOW AUTO by using a remote controller but Anti cold wind function prevails Anti cold wind cont...

Page 25: ...nd of latest defrost that evaporator high temperature protection only closes outdoor fan with the compressor still running add up to 90 minutes 8 9 2 Conditions of defrost ending Defrosting ends when...

Page 26: ...he A C operates at the DRY mode with a set temp of 24 8 11 3 All protections of remote control cooling are available at forced cooling operation 8 11 4 Forced Auto function Select forced auto function...

Page 27: ...2 hours and during the next time the set temp do not change The total time is 7 hours after 7 hours the unit stops 8 13 Auto restart function In case of a sudden power failure this function automatic...

Page 28: ...nd Parameters Model MSR1 21HRN1 QB8 MSR1 24HRN1 QB8 I3SEC 14A 18A I5MIN 20A 24A IFAN 22A 26A TE1 25 25 TE2 32 32 TE3 30 30 TE4 20 20 TE5 2 2 TE6 12 12 TE7 63 63 TE8 57 57 TE9 50 50 ANGLCOOL 67 67 ANGL...

Page 29: ...or illuminates while the air conditioner is in economic operation 10 2 Troubleshooting For models adopting electrical function Failure phenomenon Operation lamp Timer lamp Defrosting lamp Auto lamp Ov...

Page 30: ...eck if AC 220V power supply outputs to indoor PCB Check if AC 220V exists at the primary coil of transformer Yes YES No Check if AC 14 5V exists at the secondary coil of transformer Indoor PCB is defe...

Page 31: ...k if the failure realease Yes After changing indoor fan motor check if the failure realease Yes YES Yes Power supply circuit has problems Indoor PCB is defective 10 5 Over current protection of the co...

Page 32: ...e indoor PCB or change EEPROM if it s changeable 10 9 Indoor unit communication error Check the if the signal wire is well connection Change indoor PCB and check if the error is still exit Connect the...

Page 33: ...25 10 52 3 1918 1 37 1988 26 9 5507 53 3 0707 0 35 2024 27 9 1245 54 2 959 1 33 3269 28 8 7198 55 2 8442 2 31 5635 29 8 3357 56 2 7382 3 29 9058 30 7 9708 57 2 6368 4 28 3459 31 7 6241 58 2 5397 5 26...

Reviews: