10.4 Protection
10.4.1 3 minutes delay at restart for compressor.
10.4.2 Sensor protection at open circuit and breaking disconnection
10.4.3 Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High
Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure information
and can’t returns to normal operation automatically.
10.4.4 Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit stops
and LED displays failure information and can’t returns to normal operation automatically.
10.4.5 The current protection of the compressor
10.5 Fan only mode
Fan speed is high/mid/low/ Auto
10.6 Cooling mode
The 4-way valve is closed at cooling mode.
The action of the compressor and the outdoor fan:(T=indoor temperature)
Auto fan at cooling mode:
Anti-freezing control to indoor evaporator at cooling mode ( T: evaporator temp. )
Summary of Contents for MSG-24CR
Page 1: ...MSG 24CR MSG 24HR MSG 30CR MSG 30HR MSG 36CR MSG 36HR...
Page 2: ......
Page 16: ...Service manual 12 5 Refrigerant cycle diagram Cooling only Heat pump mode...
Page 18: ...Service manual 14 However excludes the initial pull down stage...
Page 19: ...Service manual 15 7 Schematic diagram and Wiring diagram 7 1 Schematic diagram...
Page 20: ...Service manual 16 7 2 Wiring diagram 7 2 1 Cooling mode MSG 24CR MSG 30CR...
Page 21: ...Service manual 17 MSG 36CR...
Page 22: ...Service manual 18 7 2 2 Heating mode MSG 24HR MSG 30HR A1 A2...
Page 23: ...Service manual 19 MSG 36HR A1 A2...
Page 24: ...Service manual 20 7 2 3 Cooling mode 3 Ph MSG 30CR 3ph...
Page 25: ...Service manual 21 MSG 36CR 3ph...
Page 26: ...Service manual 22 7 2 4 Heating mode 3 Ph MSG 30HR 3ph 1 7 3 4 5 6 2...
Page 27: ...Service manual 23 MSG 36HR 3ph...