Service manual
- 38 -
10.8.5 Auto wind at heating mode (T=indoor temp.)
10.8.6 Indoor evaporator high-temperature protection at heating mode
(T=indoor exchanger temp.)
10.8.7 The louver opens to Standard Angle ANGLHEAT when power is on for the first time
10.9 Defrosting mode(available for heating mode)
Defrosting condition: Defrosting starts when either of the following
①
&
②
:
①
A and B are satisfied:
A: The compressor keeps running for 40 minutes or more.
B: The temperature difference of evaporator and room temperature meets one of the following: