MCAC-RTT5T-201707
Midea R410A Tropical ClimaCreator Series Rooftop Package 50Hz
124
Refer to the following figure, loose 2 bolts, and move the electric motor to adjust belt tension. These
two bolts are used for precision adjustment.
Belt tension is measured by belt tension indicator
Calculate the deflection, deflection (L) = A/64.
Notes: L=A/64
Model
A (mm)
MRC-085HWN1-R(C)
380
MRC-100HWN1-R(C)
380
MRC-125HWN1-R(C)
560
MRC-150HWN1-R(C)
560
MRC-175HWN1-R(C)
580
MRC-200HWN1-R(C)
580
MRC-250HWN1-R(C)
480
MRC-300HWN1-R(C)
480
Measure the belt deflection force, the force should be between the values shown in the