Precaution on Installation
MLCAC-UTSM-2010-10
116
Installation
1. Precaution on Installation
1). Measure the necessary length of the connecting pipe, and make it by the following way.
a. Connect the indoor unit at first, then the outdoor unit.
Bend the tubing in proper way. Do not harm them.
Specially Notice the pipe length/height/dimension of each capacity.
Maximum pipe length
Model
Max. Length
Max. Elevation
12,000Btu/h 15m
8m
18,000Btu/h ~24,000Btu/h
25m
12m
30,000Btu/h 25m
15m
36,000Btu/h 30m
20m
48,000Btu/h~60,000Btu/h 50m
25m
Piping sizes
Model Liquid(mm)
Gas(mm)
12,000Btu/h~18,000Btu/h 6.35
12.7
24,000Btu/h~60,000Btu/h
9.52 15.9
CAUTIONS
Daub the surfaces of the flare pipe and the joint nuts with frozen oil, and wrench it for 3~4 rounds
With hands before fasten the flare nuts.
Be sure to use two wrenches simultaneously when you connect or disconnect the pipes.
Pipe gauge
Tightening torque
Flare dimension A
Min (mm) Max
Flare shape
Φ
6.35
14.2
~
17.2N.m
(144
~
176 kgf.cm)
8.3 8.7
Φ
9.52
32.7
~
39.9N.m
(333
~
407kgf.cm)
12.0 12.4
Φ
12.7
49.5
~
60.3N.m
(504
~
616kgf.cm)
15.4 15.8
Φ
15.9
61.8
~
75.4N.m
(630
~
770 kgf.cm)
18.6 19.1
Φ
19
97.2
~
118.6N.m
(990
~
1210kgf.cm)
22.9 23.3
b. The stop value of the outdoor unit should be closed absolutely (as original state). Every time you connect it, first loosen the nuts at the part
of stop value, then connect the flare pipe immediately (in 5 minutes). If the nuts have been loosened for a long time, dusts and other
impurities may enter the pipe system and may cause malfunction later. So please expel the air out of the pipe with refrigerant before
connection.
c. Expel the air after connecting the refrigerant pipe with the indoor unit and the outdoor unit. Then fasten the nuts at the repair-points.
2) Locate
The
Pipe
a. Drill a hole in the wall (suitable just for the size of the wall conduit), then set on the fittings such as the wall conduit and its cover.
b. Bind the connecting pipe and the cables together tightly with binding tapes. Do not let air in, which will cause water leakage by
condensation.
c. Pass the bound connecting pipe through the wall conduit from outside. Be careful of the pipe allocation to do no damage to the tubing.
3) Connect the pipes.
4) Then, open the stem of stop values of the outdoor unit to make the refrigerant pipe connecting the indoor unit with the outdoor unit in
fluent flow.
5) Be sure of no leakage by checking it with leak detector or soap water.
6) Cover the joint of the connecting pipe to the indoor unit with the soundproof / insulating sheath (fittings), and bind it well with the tapes to
prevent leakage.
Summary of Contents for MOU-12HDN1
Page 1: ...MIDEA LCAC 50Hz R410A DC Inverter Service Manual 2012...
Page 2: ......
Page 4: ......
Page 14: ...Dimensions MLCAC UTSM 2010 10 10 New Four way Cassette Compact 2 Dimensions 3 Service Space...
Page 20: ...Field Wiring MLCAC UTSM 2010 10 16 New Four way Cassette Compact MCA2 12HRDN1 Q MCA2 18HRDN1 Q...
Page 26: ...Service Space MLCAC UTSM 2010 10 22 Four way Cassette Type 3 Service Space For 18 48k For 60k...
Page 33: ...MLCAC UTSM 2010 10 Field Wiring Four way Cassette Type 29 10 Field Wiring Wiring chart...
Page 34: ...Field Wiring MLCAC UTSM 2010 10 30 Four way Cassette Type...
Page 45: ...MLCAC UTSM 2010 10 The Specification of Power Duct Type 41 9 The Specification of Power...
Page 46: ...Field Wiring MLCAC UTSM 2010 10 42 Duct Type 10 Field Wiring...
Page 47: ...MLCAC UTSM 2010 10 Field Wiring Duct Type 43 Air conditioner link circuit...
Page 48: ...Field Wiring MLCAC UTSM 2010 10 44 Duct Type...
Page 53: ...MLCAC UTSM 2010 10 Service Space Ceiling Floor Type 49 3 Service Space...
Page 54: ...Wiring Diagrams MLCAC UTSM 2010 10 50 Ceiling Floor Type 4 Wiring Diagrams MUB 12HRDN1...
Page 62: ...Field Wiring MLCAC UTSM 2010 10 58 Ceiling Floor Type 10 Field Wiring...
Page 63: ...MLCAC UTSM 2010 10 Field Wiring Ceiling Floor Type 59 For model 12...
Page 64: ...Field Wiring MLCAC UTSM 2010 10 60 Ceiling Floor Type For model 18 60...
Page 66: ......
Page 68: ...Dimensions MLCAC UTSM 2010 10 64 Console Type 2 Dimensions MFA 12HRDN1 MFA 18HRDN1...
Page 69: ...MLCAC UTSM 2010 10 Service Space Console Type 65 3 Service Space...
Page 75: ...MLCAC UTSM 2010 10 The Specification of Power Console Type 71 9 The Specification of Power...
Page 76: ...Field Wiring MLCAC UTSM 2010 10 72 Console Type 10 Field Wiring...
Page 77: ...MLCAC UTSM 2010 10 Field Wiring Console Type 73...
Page 81: ...MLCAC UTSM 2010 10 Service Space Outdoor Units 77 2 Service Space...
Page 83: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 79 4 Wiring Diagrams MOU 12HDN1...
Page 84: ...Wiring Diagrams MLCAC UTSM 2010 10 80 Outdoor Units MOUA 18HDN1 C0 MOUB 24HDN1...
Page 85: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 81 MOU 30HDN1 MOUB 36HDN1 Q MOU 48HDN1...
Page 86: ...Wiring Diagrams MLCAC UTSM 2010 10 82 Outdoor Units MOUB 36HDN1 R MOUB 48HDN1 R MOUD 60HDN1 R...
Page 87: ...MLCAC UTSM 2010 10 Wiring Diagrams Outdoor Units 83 MOUA 60HRDN1...
Page 108: ...Troubleshooting MLCAC UTSM 2010 10 104 Outdoor Units 10 3 2 10 P0 malfunction...
Page 109: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 105 10 3 2 11 P1 malfunction Only for 30K 60K...
Page 110: ...Troubleshooting MLCAC UTSM 2010 10 106 Outdoor Units 10 3 2 12 P2 malfunction Only for 30K 60K...
Page 111: ...MLCAC UTSM 2010 10 Troubleshooting Outdoor Units 107 10 3 2 13 P3 malfunction...
Page 130: ...Control MLCAC UTSM 2010 06 126 Control Part 5 Control 1 Wireless Remote Controller 127...