33
5). Operate the air conditioner at the cooling cycle and stop it when the gauge indicates 0.1MPa.
6). Set the 3-way valve to the closed position immediately
Do this quickly so that the gauge ends up indicating 0.3 to 0.5Mpa.
Disconnect the charge set, and tighten the 2-way and 3-
way valve’s stem nuts.
Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
2. Air purging by the refrigerant
Procedure:
1). Confirm that both the 2-way and 3-way valves are set to the closed position.
2). Connect the charge set and a charging cylinder to the service port of the 3-way valve
Leave the valve on the charging cylinder closed.
3). Air purging.
Open the valves on the charging cylinder and the charge set. Purge the air by loosening the flare nut on
the 2-
way valve approximately 45’ for 3 seconds then closing it for 1 minute; repeat 3 times.
After purging the air, use a torque wrench to tighten the flare nut on the 2-way valve.
4). Check the gas leakage
Check the flare connections for gas leakage.
5). Discharge the refrigerant.
Summary of Contents for MOC-09CFN1-BS0W
Page 1: ...9ASUL A1 1211 SERVICE MANUAL MIDEA AIRCONDITIONER DC INVERTER SPLIT WALL MOUNTED TYPE...
Page 17: ...15 MS9A 18HRDN1 MP0W MS9A 18CRDN1 MS0W MS9A 18HRDN1 MS0W MS9A 24HRDN1 MP0W...
Page 18: ...16 MS9A 09HRDN1 BQ0W MS9A 12HRDN1 BS0W B...
Page 19: ...17 MS9A 24CRDN1 MP0W...
Page 20: ...18 MS9A 24HRDN1 MS0W...
Page 22: ...20 MOC 12CRDN1 MS0W MOC 12HRFN1 MS0W...
Page 23: ...21 MOF 18HDN1 MP0W MOF 18CRFN1 MS0W...
Page 24: ...22 MOF 18HRFN1 MS0W MOG 24HDN1 MP0W...
Page 25: ...23 MOC 09HFN1 BQ0W MOC 12HFN1 BS0W MOF 24HDN1 MP0W...
Page 26: ...24 MOG 24HDN1 MS0W MOF 24CDN1 MP0W...
Page 58: ...56 E4 Reserved function...
Page 72: ...70...