Service
manual
10.4 Operation Modes and Functions
10.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and no setting temperature is displayed.
(3) Indoor fan can be set to Au, 20,
40,60,80 or F.
(4) The louver operates same as in cooling mode.
(5) Auto fan:
T 1 -T s
10.4.2 Cooling Mode
10.4.2.1 Compressor running rules
When T1- Ts <
∆
T -2
℃
, the compressor will stop,
when T1
—
Ts >
∆
T -0.5
℃,
the compressor will be activated.
∆
T is the programmed parameter of temperature compensation.
When the AC run in mute mode, the compressor will run with low frequency.
10.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different.
T 4
A +
A
B
C
D
E