39
cooling mode ,defrosting mode and the current protection.
8.4.3.3 Indoor fan running rules:
When the compressor is off because off the room temperature rising or the protection, the indoor fan
will run at breeze.
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind
function has the priority.
Anti-cold wind function:
When evaporator coil temp.T2 is getting higher,
T2>TE2, the indoor fan will run at setting speed.
TE1<T2<TE2, the indoor fan will run at low speed.
When T2 is getting lower,
TE4<T2<TE3,the indoor fan will run at low speed.
T2<TE4, the indoor fan will shut off.
While TE1=28
,TE2=3
℃
8
,TE3=30
,TE4=2
℃
℃
0
℃
for MSX-07HRN1-QC2, MSX-09HRN1-QC2
models.
TE1=31
,TE2=36
,TE3=30
,TE4=20
℃
℃
℃
℃
for MSX-12HRN1-QC2 model(2T0032500185)
TE1=31
℃
,TE2=36
℃
,TE3=30
℃
,TE4=22
℃
for MSX-12HRN1-QC2 model(2T0032500006)
TE1=34
,TE2=3
℃
7
,TE3=30
,TE4=20
for
℃
℃
℃
MSX-18HRN1-QC2 model.
TE1=25
℃
,TE2=32
℃
,TE3=30
℃
,TE4=20
℃
for MSX-21HRN1-QB8W, MSX-24HRN1-QB8W models.
Auto fan action: