![Midea MIV V4+ Mini Service Manual Download Page 52](http://html1.mh-extra.com/html/midea/miv-v4-mini/miv-v4-mini_service-manual_1790806052.webp)
MIV V4+ Mini DC Inverter R410A (220V, 8 kW)
DM12-01.01.05en
50
Installation
3. Installation of Outdoor Unit
3.1 Installation place
Please keep away from the following place, or malfunction of the machine may be caused:
There is combustible gas leakage.
There is much oil (including engine oil) ingredient.
There is salty air surrounding (near the coast)
There is caustic gas (the sulfide, for example) existing in the air (near a hot spring)
A place the heat air expelled out from the outdoor unit can reach your neighbor’s window.
A place that the noise interferes your neighbors every day life
A place that is too weak to bear the weight of the unit
Uneven
place.
Insufficient ventilation place.
Near a private power station or high Frequency equipment.
Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from TV set or radio to
prevent noise or Install indoor unit, outdoor unit, power cord and connecting wire at least 1m away from
TV set or radio to prevent noise or
The insulation of the metal parts of the building and the air conditioner should comply with the regulation of
National Electric Standard.
CAUTION
Keep indoor unit, outdoor unit, power supply wiring and transmission wiring at least 1 meter away from
televisions and radios. This is to prevent image interference and noise in those electrical appliances. (Noise
may be generated depending on the conditions under which the electric wave is generated, even if 1 meter is
kept.)
3.2 Installation space
>30cm
>60cm
>3
0c
m
>
20
0c
m
(Wall or obstacle)
Maintain channel
Air outlet
Air inlet
Air inlet
A
C
B
3.3 Moving and installation
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a
sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications of the outdoor units.
(refer to Fig.5-4)
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong
wind.
(refer to Fig.5-4)
Summary of Contents for MIV V4+ Mini
Page 1: ...DM12 01 01 05en Service manual MIV V4 Mini DC INVERTER R410A 220V 50Hz 1Ph MVUH80A VA1 ...
Page 2: ...Contents Part 1 General Information 1 Part 2 Outdoor Units 6 Part 3 Installation 44 ...
Page 23: ...DM12 01 01 05en MIV V4 Mini DC Inverter R410A 220V 8 kW Outdoor units 21 10 Operation Limits ...