4 Leakage test: After the vacuum degree reaches -755mmHg, stop vacuum drying and keep the pressure
for 1 hour. If the indicator of vacuum gauge does not go up, it is qualified. If going up, it indicates that
there is moisture or leak source.
8. Additional refrigerant charge
After the vacuum drying process is carried out, the additional refrigerant charge process need to be
performed.
The outdoor unit is factory charged with refrigerant. The additional refrigerant charge volume is decided
by the diameter and length of the liquid pipe between indoor and outdoor unit. Refer the following
formula to calculate the charge volume.
Diameter of liquid pipe (mm)
Φ
6.35
Φ
9.52
Φ
12.7
Formula
V=11g/m×(L-5) V=30g/m×(L-5) V=60g/m×(L-5)
V:
Additional refrigerant charge volume (g).
L :
The length of the liquid pipe (m).
Note:
Refrigerant may only be charged after performed the vacuum drying process.
Always use gloves and glasses to protect your hands and eyes during the charge work.
Use electronic scale or fluid infusion apparatus to weight refrigerant to be recharged.
Be sure to avoid
extra refrigerant charged, it may cause liquid hammer of the compressor or protections.
Use supplementing flexible pipe to connect refrigerant cylinder, pressure gauge and outdoor unit. And
The refrigerant should be charged in liquid state. Before recharging, The air in the flexible pipe and
manifold gauge should be exhausted.
After finished refrigerant recharge process, check whether there is refrigerant leakage at the connection
joint part.(Using gas leakage detector or soap water to detect).
9. Engineering of insulation
9.1 Insulation of refrigerant pipe
9.1.1 Operational procedure of refrigerant pipe insulation
Cut the suitable pipe
→
insulation (except joint section)
→
flare the pipe
→
piping layout and connection
→
vacuum drying
→
insulate the joint parts
9.1.2 Purpose of refrigerant pipe insulation
During operation, temperature of gas pipe and liquid pipe shall be over-heating or over-cooling
extremely. Therefore, it is necessary to carry out insulation; otherwise it shall debase the performance
of unit and burn compressor.
Gas pipe temperature is very low during cooling. If insulation is not enough, it shall form dew and cause
leakage.
Temperature of gas pipe is very high (generally 50-100
℃
) during heating. Insulation work must be
carried out to prevent hurt by carelessness touching.
9.1.3 Insulation material selection for refrigerant pipe
The burning performance should over 120
℃
According to the local law to choose insulation materials
The thickness of insulation layer shall be above 10mm.If in hot or wet environment place, the layer of
insulation should be thicker accordingly.
9.1.4 Installation highlights of insulation construction
Gas pipe and liquid pipe shall be insulated separately, if the gas pipe and liquid pipe were insulated
together; it will decrease the performance of air conditioner.
Summary of Contents for MHF-18HWN1-Q
Page 1: ...Contents i R410A ON OFF SERIES Service Manual 2013 LEUS B 1306...
Page 2: ......
Page 4: ......
Page 17: ...Wiring Diagrams Duct Type 13 4 Wiring Diagrams MHF 18HWN1 Q...
Page 18: ...Wiring Diagrams 14 Duct Type MHF 24HWN1 Q...
Page 19: ...Wiring Diagrams Duct Type 15 MHF 30HWN1 Q MHF 36HWN1 Q...
Page 20: ...Wiring Diagrams 16 Duct Type MHF 30HWN1 R MHF 36HWN1 R MHF 48HWN1 R MHF 60HWN1 R...
Page 21: ...Wiring Diagrams Duct Type 17...
Page 27: ...Field Wiring Duct Type 23 10 Field Wiring MHF 18HWN1 Q...
Page 32: ...Service Space 28 Ceiling Floor Type 3 Service Space...
Page 33: ...Wiring Diagrams Ceiling Floor Type 29 4 Wiring Diagrams MUE 36HRN1 Q...
Page 34: ...Wiring Diagrams 30 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Page 37: ...Field Wiring Ceiling Floor Type 33 9 Field Wiring MUE 36HRN1 Q...
Page 38: ...Field Wiring 34 Ceiling Floor Type MUE 36HRN1 R MUE 48HRN1 R MUE 60HRN1 R...
Page 45: ...Service Space Super slim Cassette Type 41 3 Service Space 1000mm 1000mm 1000mm 1000m m...
Page 46: ...Wiring Diagrams 42 Super slim Cassette Type 4 Wiring Diagrams MCD 18HRN1 Q...
Page 47: ...Wiring Diagrams Super slim Cassette Type 43 MCD 24HDN1 Q...
Page 48: ...Wiring Diagrams 44 Super slim Cassette Type MCD 36HDN1 R...
Page 49: ...Wiring Diagrams Super slim Cassette Type 45 MCD 48HDN1 R MCD 60HDN1 R...
Page 54: ...Field Wiring 50 Super slim Cassette Type 9 Field Wiring MCD 18HRN1 Q...
Page 55: ...Field Wiring Super slim Cassette Type 51 MCD 24HRN1 Q MCD 36HRN1 R MCD 48HRN1 R MCD 60HRN1 R...
Page 60: ...Wiring Diagrams 56 High Static Pressure Duct Type 4 Wiring Diagrams MHG 24HWN1 Q...
Page 61: ...Static Pressure High Static Pressure Duct Type 57 5 Static Pressure 24 000Btu h...
Page 66: ...Field Wiring 62 High Static Pressure Duct Type 10 Field Wiring MHG 24HWN1 Q...
Page 73: ...Wiring Diagrams Outdoor Units 69 4 Wiring Diagrams MOU 18HN1 Q...
Page 74: ...Wiring Diagrams 70 Outdoor Units MOU 24HN1 Q MOU 30HN1 Q...
Page 75: ...Wiring Diagrams Outdoor Units 71 MOU 30HN1 R MOU 36HN1 Q...
Page 76: ...Wiring Diagrams 72 Outdoor Units MOU 36HN1 R...
Page 77: ...Wiring Diagrams Outdoor Units 73 MOU 48HN1 R...
Page 78: ...Wiring Diagrams 74 Outdoor Units MOUA 60HN1 R...