R410a tropical air-cooled scroll chiller unit 60Hz MCAC-ATSM-2014-09
146 Installation
5. TRIAL RUN
5.1 Points for attention prior to trial run
After the water system pipeline is flushed several times, please make sure that the purity of water meets the
requirements; the system is re-filled with water and drained, and the pump is started up, then make sure that
water flow and the pressure at the outlet meet the requirements.
The unit is connected to the main power 12 hours before being started up, to supply power to the heating belt
and pre-heat the compressor. Inadequate pre-heating may cause damages to the compressor.
Set up the wired controller. See details of the manual concerning setting contents of the controller, including
such basic settings as refrigerating and heating mode, manual adjustment and automatic adjustment mode
and pump mode. Under normal circumstances, the parameters are set around standard operating conditions
for trial run, and extreme working conditions should be prevented as much as possible.
Carefully adjust the target flow controller on the water system or the inlet stop valve of the unit, to make the
water flow of the system be 90% of the water flow specified as below Table.
Summary of Contents for MGBT-D25W/DN1
Page 34: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 4 3 MGBT F120W DN1...
Page 38: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 5 3 MGBT F120W DN1...
Page 47: ...MCAC ATSM 2014 09 R410a tropical air cooled scroll chiller unit 60Hz Capacity tables 47...
Page 50: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 56: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09...
Page 60: ...R410a tropical air cooled scroll chiller unit 60Hz MCAC ATSM 2014 09 88...