R410a Full DC Inverter Mini VRF MCAC-VTSM-2013-12
14 Specifications & Performance
Sale Model
MDV-V140W/DN1
MDV-V160W/DN1(B)
MDV-V180W/DN1
Insulation class
E
E
E
Outdoor Fan
motor
Safe class
IP23
IP23
IP23
Input
W
2*100
2*100
2*100
Output
W
2*85
2*85
2*85
Rated current
A
2*0.9
2*0.9
2*0.9
Speed
r/min
800
800
800
Outdoor fan
Material
ASG20
ASG20
ASG20
Type
Axial fan
Axial fan
Axial fan
Diameter
mm
508
508
508
Height
mm
170
170
170
Outdoor coil
Number of rows
2
2
2
Tube pitch(a)
×
row pitch(b)
mm
25.4
×
22
25.4
×
22
25.4
×
22
Fin spacing
mm
1.6
1.6
1.6
Fin type (code)
Hydrophilic aluminum
Tube outside
diameter and type
mm
Ф7.94
Ф7.94
Ф7.94
Inner groove tube
Inner groove tube
Inner groove tube
Coil length
×
height
mm
1276
×
870
1276
×
870
1276
×
870
Number of circuits
7
7
7
Outdoor air flow
m
3
/h
6000
6000
6800
Outdoor sound level(sound pressure
level )
dB(A)
57
57
59
Indoor unit connectable (total capacity)
45%~130%
45%~130%
45%~130%
Max. quantity of indoor unit
6
7
9
Outdoor unit
Dimension
(W
×
H
×
D)
mm
900
×
1327
×
320
900
×
1327
×
320
900
×
1327
×
320
Packing
(W
×
H
×
D)
mm
1030
×
1456
×
435
1030
×
1456
×
435
1030
×
1456
×
435
Net/Gross weight
kg
95/106
100/111
107/118
Refrigerant
Type
R410A
R410A
R410A
Charged volume
g
3900
3900
4500
Throttle type
Electronic expansion
valve
Electronic expansion
valve
Electronic
expansion
valve
Design pressure
MPa
4.4/2.6
4.4/2.6
4.4/2.6
Refrigerant
piping
Liquid side/ Gas
side
mm
Ф9.53/Ф15.9
Ф9.53/Ф19.1
Ф9.53/Ф19.1
Max. refrigerant
pipe length
m
100
100
100
Max. difference in
level
m
8
8
8
Connection
wiring
Power wiring
mm
2
3 core
×
4.0
3 core
×
4.0
3 core
×
4.0
Signal wiring
mm
2
3 core shielded wire
×
0.75
3 core shielded wire
×
0.75
3 core shielded wire
×
0.75
Ambient temperature
℃
(
Cooling -15
~
48
)(
Heating -15
~
27
)
Notes:
1. The cooling conditions: indoor temp.: 27
℃
DB(80.6
℉
), 19
℃
WB(60
℉
) outdoor temp.: 35
℃
DB(95
℉
) equivalent pipe length:
5m drop length: 0m.
2. The heating conditions: indoor temp.: 20
℃
DB(68
℉
), 15
℃
WB(44.6
℉
) outdoor temp.: 7
℃
DB(42.8
℉
) equivalent pipe length:
5m drop length: 0m.
3. Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of *m(1m for 80/105
model,1.2m for 120~160 model). During actual operation, these values are normally somewhat higher as a result of ambient
conditions.
4. The above data may be changed without notice for future improvement on quality and performance.