Tk=Ts+Tc-1.
8.4.3.2 Outdoor fan running rules:
The outdoor units have single fan speed. The outdoor fan will run following the compressor except
when AC is in evaporator high temp. protection in heating mode ,defrosting mode and the current
protection.
8.4.3.3 Indoor fan running rules:
Indoor fan can be set to high/med/low/auto when the compressor is on. And when the compressor is
off, the indoor fan will run at low speed and the louver will locate at the anti cold wind angle.
Anti-cold wind function:
When evaporator coil temp.T2 is getting higher,
T2>TE2, the indoor fan will run at setting speed.
TE1<T2<TE2, the indoor fan will run at low speed.
When T2 is getting lower,
TE4<T2<TE3,the indoor fan will run at low speed.
T2<TE4, the indoor fan will shut off.
Auto fan action:
When T1-Ts>2
℃
,the indoor fan will run at low speed.
When T1-Ts
≤0
℃
, the indoor fan will run at medium speed.
Summary of Contents for MA9A-24HR-QB4W
Page 19: ...17 MS9A 18CR QB6...
Page 20: ...18 MS9A 18CR PC4W A MS9A 05CR QD0 MS9A 09CR QB6 A MS9A 09CR QB6 MS9A 09CR QC0 MS9A 09CR QC4 A...
Page 21: ...19 MS9A 12CR QC4 A MS9A 18CR QC0 MS9A 18CR QC2 MS9A 18CR QB8 MS9A 18CR QC4 A MS9A 18CR QC0 A...
Page 22: ...20 MS9A 21HR QB6W MA9A 24HR QB4W MS9A 22CR QC0 MS9A 22CR QB8...
Page 23: ...21 5 2 Outdoor Units MOK2 07C QB6 MOK6 09C QB6 MOA1 12C QB6 MOA2 12C QB6...
Page 24: ...22 MOB 18C QB6...
Page 25: ...23 MOK 07H QB6 MOK3 09H QB6 MOB 12H QB6 MOA1 12H QB4 MOA2 12H QB6...
Page 27: ...25 MOB3 18C QB8 MOC2 18C QC0 MOB1 18CP QC0 MOB2 18CP QC0...
Page 28: ...26 MOB 18H QB6...
Page 29: ...27 MOF 18C QC4W MOF4 21H QB6W...