33
Press " ▲ " or " ▼ " to select item to be set and press " ◄ " or " ► " to set value (setting
range 2-20s, default 5s, adjust interval 1s). Press "
" to confirm. Back to homepage if
there is no operation within 60s. The setting range of "E9 DETECTION METHOD" is 1-2,
default 1 (Method1: detect after pump starting. Method 2: detect before and after pump
starting.)
Inverter pump output setting:
Select "INV PUMP RATIO" and entry the following page to select pump: Use in the case of
multiple pumps, do not send instructions for single pump.
INV PUMP RATIO
MIN RATIO
MAX RATIO
70
%
OK
100
%
Press " ▲ " or " ▼ " to select item to be set and press" ◄ " or " ► " to set value. Press
"
" to confirm. Back to homepage if there is no operation within 60s. MINRATIO setting
should ensure its flow meet the requirement of the whole unit, otherwise the unit may be
damaged.
MIN RATIO
MINIMUM RATIO
40
∽
MAX RATIO
MAX RATIO
MAXIMUM RATIO
Max (70%, MIN RATIO)
∽
100%
CHECK PARTS
Select "CHECK PARTS" and press "
" to entry submenu. Display as follows: