background image

2                                                                 

Specifications subject to change without notice.                                                                         32801002001

INTRODUCTION

The Air Handler models are R-410A Fan Coils designed for 
installation flexibility allowing multi-position installation Upflow, 
down flow, horizontal right & horizontal left. These units leave the 
factory compliant with low leak requirements of

 

less than 2% cabinet 

leakage rate at 0.5 inches W.C. when tested in accordance with 
ASHRAE 193 standard.

The metering device is installed on the outdoor unit and the fan coils 
do not have the device. All fan coils have a DC fan motor with 
variable speeds for efficiency. The units have been designed for up-
flow, down-flow, and horizontal orientations, including manufactured 
and mobile home applications.

These units require a field supplied air filter and electrical disconnect* 
and are designed specifically for R-410A refrigerant heat pumps. 
These units are available for systems of 24,000 through 48,000 BTUh 
nominal cooling capacity (depending on the local codes) See “Step 8 - 
Electrical Connections” on page 16

HEATER PACKAGES

This unit is not equipped with an electric heater package. A factory-
approved, field-installed, ETL listed heater package is available from 
your equipment supplier. Factory-authorized, field-installed electric 
heater packages are available in sizes 5kW through 20kW. Electric 
heaters that are not factory approved could cause damage which 
would not be covered under the equipment warranty. Review the 
product data literature for all available accessory kits.

Table 1 — Indoor Unit Model Numbers

ACCESSORIES

The system is shipped with the following accessories (see Table 2). Use 
all of the installation parts and accessories to install the system. Improper 
installation may result in water leakage, electrical shock and fire, or cause 
the equipment to fail. Keep the installation manual in a safe place and do 
not discard any accessories until the installation has been completed.

Table 2 — Accessories 

NOTE: In order to use the Wireless Remote for Air Flow Adjust-
ment or Static Pressure setting, the outer panel and control panel 
cover must be removed to make the IR Receiver accessible. See 
“Step 10 - Setting Static Pressure and Airflow” on page 20.

Fig. 2 — Air Handler

Fig. 3 — Indoor Unit Representation

KBTUH

V-PH-HZ

ID MODEL NO.

24

208/230-1-60

DLFSAAH24XAK

36

DLFLAAH36XAK

48

DLFLAAH48XAK

EXPLOSION HAZARD

Failure to follow this warning could 

result in death, serious personal injury, 

and/or property damage.
Never use air or gases containing oxygen 

for leak testing or operating refrigerant 

compressors. Pressurized mixtures of air 

or gases containing oxygen can lead to 

an explosion.

WARNING

INSTALLATION

Entrust a licensed contractor to install the unit. Installation by 
unskilled persons may lead to improper installation, electric shock, 
or fire. Re-installation must be performed by authorized 
professionals. Non-compliance may lead to electric shock or fire.

WARNING

This unit is 

NOT

 equipped with a single point electrical 

connection for an Auxiliary Heat Package. A separate power 
supply is required for the Auxiliary Heat Package.

CAUTION

NAME

SHAPE

QUANTITY

Owner’s and 

Installation 

Manual

1

Wireless Remote 

Controller*

1

Battery

1

Infrared Display Panel 

(located in the 

Air Handler Unit)

1

ON/OF F

T E MP

FP

TIMER
  ON

TIMER
  OFF

MODE

FAN/SLC

SLEEP

TURBO

SWING

DIRECT

CLEAN

LED

FOLLOW

Air outlet

Air inlet

Drain connection

Refrigerant 
connecting 
pipe

Coil Compartment

(Access Panel Removed)

Upflow Drain Pan

Horizontal Drain Pan

Summary of Contents for DLFLAA

Page 1: ...work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in the literature and attached to the unit Consult local building codes a...

Page 2: ...allation parts and accessories to install the system Improper installation may result in water leakage electrical shock and fire or cause the equipment to fail Keep the installation manual in a safe p...

Page 3: ...84 11 8 299 13 3 339 3 0 75 2 5 64 4 9 124 6 8 174 1 7 44 A HEIGHT 48 1 1222 C WIDTH 19 7 501 4 8 121 2 4 61 6 7 171 2 2 57 D DUCT 18 2 462 E DUCT 10 3 262 B DEPTH 21 1 535 0 8 21 0 5 13 0 6 16 18 4...

Page 4: ...med according to the installation instructions Improper installation can cause water leakage electrical shock or fire In North America installation must be performed in accordance with the requirement...

Page 5: ...t is installed over a finished ceiling and or living area building codes may require a field supplied secondary condensate pan to be installed under the entire unit Some localities may allow as an alt...

Page 6: ...t 5 Install the drain lines Fig 7 Vertical Upflow Installations Fig 8 Horizontal Right Installations NOTE For a horizontal right installation secondary condensate pan field supplied must be installed...

Page 7: ...d drain pan assembly 9 Reinstall the pipe temperature sensor in its original position Attach the room temperature sensor to the evaporator output pipe protection sleeve Fig 15 Reinstall the Pipe Tempe...

Page 8: ...uipped with the electric auxiliary heat module please check the electric auxiliary heat module specification that is compatible with the unit to avoid unnecessary consequences caused by improper match...

Page 9: ...into the opening made by removal of the sheet metal cover s Ensure the two support rod ends are on the opposite bulkhead Fig 24 Insert Heating Module 5 Use the 3 screws 6 screws for 15K or 20K remove...

Page 10: ...quirements and local codes see Table 6 on page 11 Choose the power cord and the power cord installation location see Figure 30 Each circuit breaker group needs to connect to the power input line Where...

Page 11: ...do not have a 90 degree elbow and 10ft 3m of main duct to first branch takeoff may require internal acoustical insulation lining As an alternative fibrous ductwork may be used if constructed and insta...

Page 12: ...ood 2 Use a 2 5in 65mm core drill to drill a hole in the wall Make sure the hole is drilled at a slight downward angle so that the outdoor end of the hole is lower than the indoor end by about 0 5in 1...

Page 13: ...g an airtight seal a After removing the burrs from the cut pipe seal the ends with PVC tape to prevent foreign materials from entering the pipe b Sheath the pipe with insulating material c Place flare...

Page 14: ...nder to prevent kinking or damaging the tubing 6 After connecting the copper pipes to the outdoor unit wrap the power cable signal cable and the piping together with binding tape NOTE While bundling t...

Page 15: ...ost positive way of assuring a system is free of air and moisture see Fig 49 NOTE DO NOT add a filter line drier Fig 49 Deep Vacuum Graph Triple Evacuation Method The triple evacuation method should b...

Page 16: ...it would lose power A disconnect switch is not required on the indoor unit side on the wiring between the outdoor and indoor unit A 3 pole disconnect purchased separately may be used for extra protect...

Page 17: ...e is a ground wire To minimize voltage drop the factory recommended wire size is 14 2 power stranded with a ground Communication Wiring A separate 2 wire cable stranded shielded copper conductor with...

Page 18: ...0 5 0 20 120 36 5 0 42 250 48 5 0 65 400 3 S 1 L1 2 L2 208 230 1 60 Power Supply Main 1 L1 208 230 1 60 2 L2 3 S 1 L1 2 L2 CONNECTING CABLE OUTDOOR TO INDOOR Indoor Unit Power Supply 208 230 1 60 Indo...

Page 19: ...Indoor Unit Control Box Sizes 36 48 LED Display The control displays active faults codes on the LED display When the control displays the fault code and the LED flashes quickly there is something wro...

Page 20: ...nnected b Turn off the power to the indoor and outdoor units for 3 minutes c Turn the power back on Wait 1 minute and check the 24 volt Interface digital display If the display reads 00 then proceed I...

Page 21: ...troller exits the MODIFICATION mode After you power OFF the unit power the unit ON again and the unit retains the setting value Fig 65 RG57 Remote Controller FP Activate Disable freeze protection func...

Page 22: ...1 400 1 310 1 215 1 105 950 825 Low 1 525 1 450 1 372 1 280 1 190 1 074 935 785 650 36 SP1 High 1 335 1 270 1 165 1 062 950 810 645 450 240 Medium 1 185 1 100 990 845 685 520 335 Low 1 020 915 775 60...

Page 23: ...Pressurein WC High Medium Low SP4 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta cPressurein WC High Medium Low SP1 0 200 400 600 800 1 000 1...

Page 24: ...M Sta cPressurein WC High Medium Low SP2 0 200 400 600 800 1 000 1 200 1 400 1 600 1 800 2 000 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 Air ow CFM Sta c Pressurein WC High Medium Low SP3 0 200 400 600 800...

Page 25: ...conditioner Turn off the main power switch and reinstall the test cover NOTE If the unit malfunctions or does not operate according to your expectations please refer to the Troubleshooting section of...

Page 26: ...FF E0 Indoor unit EEPROM parameter error 2 times OFF E1 Indoor outdoor unit communication error 4 times OFF E3 The indoor fan speed is operating outside of the normal range 5 times OFF E4 Indoor room...

Reviews: