When the air conditioner enters the information enquiry status, it displays the code value for 25 seconds (see Table 10).
Table 10—Information Enquiry
ENQUIRY
INFORMATION
DISPLAY VALUE
MEANING
REMARK
T1,T2,T3,T4,
T2B,TP,TH,
Targeted
Frequency,
Actual
Frequency
-1F,-1E,-1d,-1c,
-1b,-1A
-25,-24,-23,-22,-21,-20
1. The displaying temperature is the actual value.
2. The temperature is
_
C no matter what kind of remote con
troller is used.
3. T1,T2,T3,T4,T2B display range:-25~70, TP display
range:-20~130.
4. Frequency display range: 0~159HZ.
5. If the actual value exceeds the range, it displays the
maximum value or minimum value.
-19
—
99
-19
—
99
A0,A1,
…
A9
100,101,
…
109
b0,b1,
…
b9
110,111,
…
119
c0,c1,
…
c9
120,121,
…
129
d0,d1,
…
d9
130,131,
…
139
E0,E1,
…
E9
140,141,
…
149
F0,F1,
…
F9
150,151,
…
159
Indoor fan speed
/Outdoor fan speed
0
OFF
1,2,3,4
Low speed, Medium speed, High
speed, Turbo
For some big capacity motors.
14-FF
Actual fan speed = Display value
turns to decimal value and then
multiply 10. The unit is RPM.
For some small capacity motors, the display value is from 14-FF
(hexadecimal), the corresponding fan speed range
is from 200-2550 RPM.
EXV opening angle
0-FF
Actual EXV opening value =
Display value turns to decimal
value and then multiply 2.
Compressor
continuous running
time
0-FF
0-255 minutes
If the actual value exceeds the range, it displays the
maximum value or minimum value.
Compressor stop
causes
0-99
For the detailed meaning, please
consult with engineer
Decimal display
Reserve
0-FF