background image

IM-DHMSHA-02                                                                            Specifications subject to change without notice.                                                                                         

13

FINAL TUBING CHECK

IMPORTANT:

 Ensure the certain factory tubing on the indoor unit

has  not  shifted  during  shipment.  Ensure  the  tubes  are  not  rubbing

against each other or  any sheet metal. Pay close  attention to feeder

tubes and ensure the wire ties on the feeder tubes are secure and tight.

DRAIN CONNECTIONS

Connect the drain line. The drain line must not have a trap anywhere

in its length, must pitch downwards, and must be insulated up to the

outside wall (see Fig. 20). By default, the drain hose is attached to the

left-hand side of unit (when facing the back of the unit). However, it

can also be attached to the right-hand side.

a. To ensure proper drainage, attach the drain hose on the 

same side that your refrigerant piping exits the unit.

b. Attach a drain hose extension (purchased separately) to the 

end of the drain hose.

c. Wrap the connection point firmly with Teflon tape to 

ensure a good seal and to prevent leaks.

d. For the portion of the drain hose that remains indoors, wrap 

it with foam pipe insulation to prevent condensation.

e. Remove the air filter and pour a small amount of water into 

the drain pan to ensure that water flows from the unit 

smoothly.

Plug the Unused Drain Hole

To prevent unwanted leaks, plug the unused drain hole with the rubber

plug provided.

Fig. 20 — Proper Drain Hose Installation

NOTE: For proper orientation of the refrigerant piping, 

electrical cable and drain lines, refer to Fig. 21.

Fig. 21 — Bundle drain hose, refrigerant pipes, and 

signal cable

NOTE: The factory insulation provided with the product is 

sufficient, therefore adding additional insulation to 

the refrigerant pipes is NOT recommended. 

Additional insulation may keep the product from 

attaching flush to the wall.

NOTE: For applications where gravity cannot be used for 

drainage, a condensate pump accessory is 

available. Consult the condensate pump 

Installation Instructions for more information.

WIRELESS REMOTE CONTROL 

INSTALLATION

Mounting Bracket (if installed on the wall)

1. Use the two screws supplied with the wireless remote control to

attach the mounting bracket to the wall in a location selected by the

customer and within operating range.

2. Install the batteries in the remote control.

3. Place the remote control into the remote control mounting bracket.

NOTE: For remote control operation, refer to the unit 

Owner’s Manual.

WIRED REMOTE CONTROL 

INSTALLATION

To connect the wired remote controller KSACN0101AAA (Timer 

Function) to the indoor units, connect to the 4-pin connector located 

on the display board.
To connect the wired remote controller KSACN0401AAA (7 Day 

Programmable) to the indoor units:

1. Replace the display board with the shipped with the kit.

2. Install the adapter board (shipped with the kit).

3. Connect the adapter board to the new  display board. Follow the

instructions on the wired controller KSACN0401AAA installation

instructions manual for more details.

4. Connect the female molex plug on the adapter board to the male

molex plug from the extension cable shipped with the kit. 

5. Connect the extension cable to the wired controller

For setup instructions, refer to the controller installation manual.

START-UP

Test Operation

Perform a test operation after completing a gas leak and electrical

safety check (see Fig. 22).

Fig. 22 — Test Operation

1. Push 

ON/OFF

 on the remote control to begin testing.

NOTE: A protection feature prevents the air conditioner 

from activating for approximately 3 to 4 minutes.

2. Push 

MODE

, select 

COOLING

HEATING

FAN

 mode to check

that all functions work correctly.

3. To run the test using the 

MANUAL

 button on the indoor unit:

a. Open the front panel of the indoor unit;

b. Push 

MANUAL

 once to energize the unit. The set 

conditions for manual operation are as follows:

•Preset set point: 76

F (24

C)

•Fan speed: 

AUTO

•Discharge air direction: Pre-set position based on operation

in the 

COOL

 or 

HEAT

 mode.

4. Be sure to set the 

MANUAL

 button to 

OFF

 (by pushing it twice

again) after completing the test operation.

r

e

t

a

w

 

o

t

n

i

 

d

n

e

 

n

i

a

r

d

 

t

u

p

 

t

o

n

 

o

D

r

e

p

o

r

P

Do not form a rise

Indoor Unit

Space behind unit

Refrigerant piping

Drain hose

Signal wire

Insulation tape

Manual control 

button

AUTO/COOL

Summary of Contents for DHMSHA Series

Page 1: ...l models may differ slightly TABLE OF CONTENTS SAFETY CONSIDERATIONS 2 PARTS LIST 3 SYSTEM REQUIREMENTS 4 WIRING 4 DIMENSIONS 5 CLEARANCES 9 INSTALLATION TIPS 10 INDOOR UNIT INSTALLATION 10 ELECTRICAL...

Page 2: ...NGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsaf...

Page 3: ...Part No Part Name Qty 1 Indoor Unit 1 2 Mounting Plate 1 3 Mounting Screw A ST3 9x25 C H 5 4 Anchor 5 5 Air Filter 1 6 Wireless Remote Control 1 7 Wireless Remote Control Holder 1 8 Wireless Remote C...

Page 4: ...es exists a 14 2 stranded shielded wire can be used to replace L2 N and S between outdoor unit and indoor unit landing the shield onto ground in the outdoor unit only NOTE The main power is supplied t...

Page 5: ...08 230V 208 230V 208 230V 208 230V 208 230V Height In mm 11 07 281 11 07 281 11 07 281 12 40 315 13 39 343 13 39 343 13 39 343 Width In mm 33 17 842 33 17 842 33 17 842 38 98 990 46 69 1186 46 69 1186...

Page 6: ...17 360 33 17 842 33 16 842 32 24 819 2 2 56 1 78 45 11 03 280 9 25 235 8 49 216 7 96 202 9 46 240 9 46 240 9 25 235 9 25 235 8 1 206 7 05 179 5 87 149 8 1 206 6 88 175 5 36 136 1 86 47 7 96 202 8 49...

Page 7: ...6 21 158 5 08 129 4 13 105 3 23 82 1 08 27 11 32 287 10 39 264 9 57 243 8 78 223 7 53 191 5 98 152 5 08 129 4 13 105 3 15 80 1 08 27 10 66 271 12 40 315 2 56 65 1 74 44 5 03 128 13 52 343 38 98 990 20...

Page 8: ...24 57 21 63 549 47 01 1194 20 91 531 2 24 57 2 25 57 2 24 57 13 51 343 2 25 57 12 10 307 14 98 380 14 26 362 12 54 319 11 05 281 9 71 247 4 53 115 4 34 110 4 33 110 4 53 115 9 70 246 12 53 318 14 25 3...

Page 9: ...es NOTE The top clearance recommended for proper return airflow is 5 9in 15cm Reduction of this clearance may decrease unit performance This may be reduced to 3 2in 80mm as long as the right and left...

Page 10: ...ides Attach the Mounting Plate to the Wall 1 Carefully remove the mounting plate which is attached on the back of the indoor unit 2 Using the stencil determine the wall hole position The mounting plat...

Page 11: ...iring on Indoor Unit High Wall Unit Size Indoor Fan Max Fuse CB Amp V PH HZ FLA HP Refer to outdoor unit installation instructions Indoor unit powered by the outdoor unit 12K 208 230 1 60 0 33 0 053 9...

Page 12: ...ring cover and close the indoor unit s front cover 10 Piping a Cut the pipe with a pipe cutter at 90 degrees see Fig 16 b Remove the service connection if provided with the unit Fig 16 Pipe Cutting c...

Page 13: ...cket if installed on the wall 1 Use the two screws supplied with the wireless remote control to attach the mounting bracket to the wall in a location selected by the customer and within operating rang...

Page 14: ...is a combination of flashing LEDs on the display panel or the front of the unit Some indoor units display error codes specifying failure modes in the outdoor units If possible always check the diagno...

Reviews: